TSXi Soft Starters
Our TSXi brings full three-phase SCR control, an internal bypass and adaptive starting and stopping to demanding fixed-speed motor applications. With 24–1250 A nominal selections, it is suited to industrial motor-control centres, OEM panels, conveyors, crushers, mills, compressors and pumping systems where control, monitoring and integration matter.
Control that follows the application
Choose constant-current, current-ramp or adaptive starting. Stopping options include adaptive control, timed voltage ramp, DC brake and soft brake. Adaptive control adjusts acceleration or deceleration to load behaviour; it does not remove the need to size the starter for actual current and duty. Active braking and inside-delta arrangements have installation restrictions in the manual.
A dual-order thermal model tracks heat across starts and operating cycles. Protection responses can be configured as trip, soft trip, warning or log where supported. We provide dual parameter sets, metering and monitoring, a 384-event log with real-time-clock timestamps, USB parameter backup and firmware updating. Protection settings, defaults and parameter IDs remain in the source-specific tables below.
Select supply, configuration and duty together
Our current website specifies V7: 380–690 VAC for Australia and V5: 200–525 VAC for New Zealand. C1 provides separate 110–120 VAC or 220–240 VAC control supplies; C2 24 VAC/VDC is optional. The brochure's broad “Standard ANZ” label does not replace the separate regional voltage-code choices.
The 22 collected website selections link B-suffix, V7/C1-named sheets. Their first-page application forms leave industry, application, environment, voltage, motor size/FLC and starting current/time blank. We retain all model identities and source associations without filling those fields from a model number.
Use the manual's conditional IEC and NEMA tables for selection. At 1,000 m and 40°C, for example, 0024B is 24 A at AC53b 3.0-10:350, but 16 A at 4.0-20:340. Nominal current alone does not establish a heavy-start rating. The manual also contains C-suffix non-bypassed models and external-bypass arrangements; these are family reference configurations, not additional B models invented for the current website list. C models require the stated external bypass to achieve the bypassed ratings.
Mounting, protection and integration
The model-sheet protection scope is IP20 for 0024B–0135B and IP00 for 0184B–1250B. Optional finger guards do not make every starter IP20 by default. Allow model-specific space, cooling and derating for temperature above 40°C and altitude above 1,000 m. Dimension, mass, clearance, terminal and fuse tables remain edition-specific below.
Optional communication interfaces include Modbus RTU/TCP, Profinet, EtherNet/IP, Profibus and DeviceNet for PLC/SCADA integration. A pumping Smart Card adds application-specific inputs and functions; it is an option, not standard equipment on every unit. The manual permits a maximum of one expansion card at a time. Remote keypad options, ground-fault-enabled module variants and pump functions must be selected by the exact accessory code.
Operation and maintenance references
The 108-page TSXi user manual covers safety/model selection (PDF 5–9), IEC/NEMA ratings, dimensions and accessories (10–16), protection/fuses (17–24), specifications (25–26), installation (27–38), setup and logs (39–45), keypad (46–48), operation (49–60), parameter reference (61–95) and troubleshooting (96–105). Blank/end-contact pages add no model ratings. Tables below preserve the data; wiring diagrams, curves and complete procedures remain in the linked original.
Inside-delta detection is supported, but Adaptive Control, Jog, Brake and PowerThrough are not supported in inside-delta operation according to the manual. Emergency/Fire Mode and PowerThrough are exceptional operating modes. The manual warns that Emergency Mode ignores all trips and warnings, disables protection, can compromise starter or motor life, and voids the product warranty. PowerThrough uses two-phase control after an SCR fault, is available only in-line, and does not support adaptive starting or stopping. This feature is not a declaration of certified fire-pump compliance; read the manual's warnings and confirm the system design with us. Do not turn disabling protection into normal operating guidance.
Source differences to confirm
The sheets specify mains tolerance ±10%, while the brochure/manual use +10%/−15% in their supply specification. Semiconductor/HRC coordination labels are reversed between the sheet and manual. The brochure labels programmable input B 13,14 on PDF 12 and 13,15 on PDF 14. We retain those source statements without issuing a guessed wiring or fuse instruction.
The model sheets print 61.0 kg for 0835B–0940B, while the brochure and manual give 51.0 kg. Other large-model weights also differ between editions; use a confirmed outline and lifting weight for the actual unit. The brochure's accessory range includes 0654B, absent from its model table, and the model sheets use different accessory-range labels. Confirm the exact guard kit rather than inferring equivalence.
Selection and detailed reference
All 22 product selections and source files
Choose the listed configuration, then use its own datasheet and drawing. Website selections and PDF ratings remain separate where they differ. Additional files marked available upon request must be requested from us.
| Website selection | Product-specific files | Additional files |
|---|---|---|
| Current Rating: 24 | TSXi-0024B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 42 | TSXi-0042B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 52 | TSXi-0052B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 64 | TSXi-0064B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 69 | TSXi-0069B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 105 | TSXi-0105B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 115 | TSXi-0115B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 135 | TSXi-0135B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 184 | TSXi-0184B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 200 | TSXi-0200B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 229 | TSXi-0229B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 250 | TSXi-0250B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 352 | TSXi-0352B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 397 | TSXi-0397B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 410 | TSXi-0410B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 550 | TSXi-0550B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 580 | TSXi-0580B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 835 | TSXi-0835B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 940 | TSXi-0940B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 1070 | TSXi-1070B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 1230 | TSXi-1230B-V7-C1-Soft-Starter.pdf | No additional download listed |
| Current Rating: 1250 | TSXi-1250B-V7-C1-Soft-Starter.pdf | No additional download listed |
The application forms leave industry, application, environment, line voltage, motor size, maximum motor FLC, start current and start duration blank for every listed model. The printed model field omits the C1 suffix used in the download filename; confirm the full order code with us.
TSXi-0024B-V7-C1-Soft-Starter.pdf — source page 4
P054 / TSXi-0024B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0042B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0052B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0064B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0069B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0105B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0115B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0135B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0184B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0200B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0229B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0250B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0352B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0397B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0410B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0550B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0580B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0835B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-0940B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-1070B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-1230B-V7-C1-Soft-Starter.pdf — source page 4; P054 / TSXi-1250B-V7-C1-Soft-Starter.pdf — source page 4
Conditions for this section:
- C1: The printed model range limits applicability. Images, performance curves and wiring geometry require the original source.
| Specification | Value | Unit / basis | Conditions |
|---|---|---|---|
| Dimensions / TSXi-0024B~0042B / A | 152 (6.0) | mm (inches) | C1 |
| Dimensions / TSXi-0024B~0042B / B | 92 (3.6) | mm (inches) | C1 |
| Dimensions / TSXi-0024B~0042B / C | 336 (13.2) | mm (inches) | C1 |
| Dimensions / TSXi-0024B~0042B / D | 307 (12.1) | mm (inches) | C1 |
| Dimensions / TSXi-0024B~0042B / E | 231 (9.1) | mm (inches) | C1 |
| Dimensions / TSXi-0024B~0042B / Weight | 4.8 (10.7) | kg (lbs) | C1 |
| Dimensions / TSXi-0052B~0069B / A | 152 (6.0) | mm (inches) | C1 |
| Dimensions / TSXi-0052B~0069B / B | 92 (3.6) | mm (inches) | C1 |
| Dimensions / TSXi-0052B~0069B / C | 336 (13.2) | mm (inches) | C1 |
| Dimensions / TSXi-0052B~0069B / D | 307 (12.1) | mm (inches) | C1 |
| Dimensions / TSXi-0052B~0069B / E | 231 (9.1) | mm (inches) | C1 |
| Dimensions / TSXi-0052B~0069B / Weight | 4.9 (10.9) | kg (lbs) | C1 |
| Dimensions / TSXi-0105B~0135B / A | 152 (6.0) | mm (inches) | C1 |
| Dimensions / TSXi-0105B~0135B / B | 92 (3.6) | mm (inches) | C1 |
| Dimensions / TSXi-0105B~0135B / C | 336 (13.2) | mm (inches) | C1 |
| Dimensions / TSXi-0105B~0135B / D | 307 (12.1) | mm (inches) | C1 |
| Dimensions / TSXi-0105B~0135B / E | 231 (9.1) | mm (inches) | C1 |
| Dimensions / TSXi-0105B~0135B / Weight | 5.5 (12.1) | kg (lbs) | C1 |
| Dimensions / TSXi-0184B~0250B / A | 216 (8.5) | mm (inches) | C1 |
| Dimensions / TSXi-0184B~0250B / B | 180 (7.1) | mm (inches) | C1 |
| Dimensions / TSXi-0184B~0250B / C | 495 (19.5) | mm (inches) | C1 |
| Dimensions / TSXi-0184B~0250B / D | 450 (17.7) | mm (inches) | C1 |
| Dimensions / TSXi-0184B~0250B / E | 243 (9.6) | mm (inches) | C1 |
| Dimensions / TSXi-0184B~0250B / Weight | 12.7 (28.0) | kg (lbs) | C1 |
| Dimensions / TSXi-0352B~0401B / A | 216 (8.5) | mm (inches) | C1 |
| Dimensions / TSXi-0352B~0401B / B | 180 (7.1) | mm (inches) | C1 |
| Dimensions / TSXi-0352B~0401B / C | 523 (20.6) | mm (inches) | C1 |
| Dimensions / TSXi-0352B~0401B / D | 450 (17.7) | mm (inches) | C1 |
| Dimensions / TSXi-0352B~0401B / E | 243 (9.6) | mm (inches) | C1 |
| Dimensions / TSXi-0352B~0401B / Weight | 15.5 (34.2) | kg (lbs) | C1 |
| Dimensions / TSXi-0550B~0580B / A | 216 (8.5) | mm (inches) | C1 |
| Dimensions / TSXi-0550B~0580B / B | 180 (7.1) | mm (inches) | C1 |
| Dimensions / TSXi-0550B~0580B / C | 523 (20.6) | mm (inches) | C1 |
| Dimensions / TSXi-0550B~0580B / D | 450 (17.7) | mm (inches) | C1 |
| Dimensions / TSXi-0550B~0580B / E | 243 (9.6) | mm (inches) | C1 |
| Dimensions / TSXi-0550B~0580B / Weight | 19.0 (41.9) | kg (lbs) | C1 |
| Dimensions / TSXi-0835B~0940B / A | 446 (17.6) | mm (inches) | C1 |
| Dimensions / TSXi-0835B~0940B / B | 287 (11.3) | mm (inches) | C1 |
| Dimensions / TSXi-0835B~0940B / C | 618 (24.3) | mm (inches) | C1 |
| Dimensions / TSXi-0835B~0940B / D | 540 (21.3) | mm (inches) | C1 |
| Dimensions / TSXi-0835B~0940B / E | 310 (12.2) | mm (inches) | C1 |
| Dimensions / TSXi-0835B~0940B / Weight | 61.0 (134.5 | kg (lbs) | C1 |
| Dimensions / TSXi-1070B~1230B / A | 446 (17.6) | mm (inches) | C1 |
| Dimensions / TSXi-1070B~1230B / B | 287 (11.3) | mm (inches) | C1 |
| Dimensions / TSXi-1070B~1230B / C | 618 (24.3) | mm (inches) | C1 |
| Dimensions / TSXi-1070B~1230B / D | 540 (21.3) | mm (inches) | C1 |
| Dimensions / TSXi-1070B~1230B / E | 310 (12.2) | mm (inches) | C1 |
| Dimensions / TSXi-1070B~1230B / Weight | 63.0 (139.9) | kg (lbs) | C1 |
| Dimensions / TSXi-1250B / A | 446 (17.6) | mm (inches) | C1 |
| Dimensions / TSXi-1250B / B | 287 (11.3) | mm (inches) | C1 |
| Dimensions / TSXi-1250B / C | 618 (24.3) | mm (inches) | C1 |
| Dimensions / TSXi-1250B / D | 540 (21.3) | mm (inches) | C1 |
| Dimensions / TSXi-1250B / E | 310 (12.2) | mm (inches) | C1 |
| Dimensions / TSXi-1250B / Weight | 65.0 (143.3) | kg (lbs) | C1 |
Manual · PDF 8 · Model code elements
Code-element definitions; no invented full order code or availability claim.
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | Nominal current rating | 0069 shown as example |
| 2 | Bypass B | internally bypassed |
| 3 | Bypass C | non-bypassed (continuous connection) |
| 4 | Mains V5 | 200~525 VAC |
| 5 | Mains V7 | 380~690 VAC |
| 6 | Control C1 | 110~120 VAC or220~240 VAC |
| 7 | Control C2 | 24 VAC/VDC |
Manual · PDF 9 · AC53b bypassed example
Illustrative code80 A:AC-53b3.5-15:345; not a separate product rating.
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | Starter current | 80 A |
| 2 | Start current | 3.5 x motor full load current |
| 3 | Start time | 15 s |
| 4 | Off time | 345 s |
Manual · PDF 9 · AC53a non-bypassed example
Illustrative code351 A:AC-53a3.5-15:50-6; not a separate product rating.
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | Starter current | 351 A |
| 2 | Start current | 3.5 x motor full load current |
| 3 | Start time | 15 s |
| 4 | On-load duty cycle | 50% |
| 5 | Starts per hour | 6 |
Manual · PDF 10 · In-line bypassed, short off-time group
Current ratings in amperes;IEC source conditions1000 m altitude,40°C ambient. Keep installation/bypass state and exact duty header. Other operating conditions require supplier ratings. Models0735C~1220C require an external bypass contactor to achieve bypassed ratings.
| Source row | Model | 3.0-10:350 | 3.5-15:345 | 4.0-10:350 | 4.0-20:340 | 5.0-5:355 |
|---|---|---|---|---|---|---|
| 1 | 0024B | 24 | 20 | 19 | 16 | 16 |
| 2 | 0042B | 42 | 34 | 34 | 27 | 31 |
| 3 | 0052B | 52 | 41 | 39 | 34 | 34 |
Manual · PDF 10 · In-line bypassed, long off-time group
Current ratings in amperes;IEC source conditions1000 m altitude,40°C ambient. Keep installation/bypass state and exact duty header. Other operating conditions require supplier ratings. Models0735C~1220C require an external bypass contactor to achieve bypassed ratings.
| Source row | Model | 3.0-10:590 | 3.5-15:585 | 4.0-10:590 | 4.0-20:580 | 5.0-5:595 |
|---|---|---|---|---|---|---|
| 1 | 0064B | 64 | 62 | 60 | 50 | 53 |
| 2 | 0069B | 69 | 69 | 69 | 62 | 64 |
| 3 | 0105B | 105 | 86 | 84 | 68 | 76 |
| 4 | 0115B | 115 | 107 | 104 | 86 | 95 |
| 5 | 0135B | 135 | 129 | 126 | 103 | 115 |
| 6 | 0184B | 184 | 143 | 139 | 115 | 127 |
| 7 | 0200B | 200 | 170 | 165 | 138 | 150 |
| 8 | 0229B | 229 | 194 | 187 | 157 | 170 |
| 9 | 0250B | 250 | 244 | 230 | 200 | 202 |
| 10 | 0352B | 352 | 285 | 277 | 234 | 257 |
| 11 | 0397B | 397 | 322 | 311 | 262 | 288 |
| 12 | 0410B | 410 | 410 | 410 | 379 | 400 |
| 13 | 0550B | 550 | 526 | 505 | 427 | 462 |
| 14 | 0580B | 580 | 578 | 554 | 469 | 507 |
| 15 | 0835B | 835 | 654 | 630 | 535 | 592 |
| 16 | 0940B | 940 | 736 | 708 | 603 | 663 |
| 17 | 1070B | 1070 | 950 | 905 | 785 | 834 |
| 18 | 1230B | 1230 | 1154 | 1090 | 959 | 989 |
| 19 | 1250B | 1250 | 1250 | 1250 | 1155 | 1250 |
| 20 | 0735C | 835 | 732 | 716 | 593 | 695 |
| 21 | 0830C | 940 | 822 | 803 | 667 | 776 |
| 22 | 1025C | 1210 | 1067 | 1033 | 874 | 1170 |
| 23 | 1170C | 1430 | 1307 | 1252 | 1076 | 1170 |
| 24 | 1220C | 1620 | 1620 | 1616 | 1309 | 1620 |
Manual · PDF 11 · In-line non-bypassed
Current ratings in amperes;IEC source conditions1000 m altitude,40°C ambient. Keep installation/bypass state and exact duty header. Other operating conditions require supplier ratings. Source uses off-time-style headers here; clarification flag retained.
| Source row | Model | 3.0-10:590 | 3.5-15:585 | 4.0-10:590 | 4.0-20:580 | 5.0-5:595 |
|---|---|---|---|---|---|---|
| 1 | 0735C | 735 | 590 | 572 | 492 | 542 |
| 2 | 0830C | 830 | 667 | 645 | 557 | 609 |
| 3 | 1025C | 1025 | 839 | 805 | 710 | 751 |
| 4 | 1170C | 1170 | 979 | 934 | 838 | 862 |
| 5 | 1220C | 1220 | 1134 | 1109 | 964 | 1075 |
Manual · PDF 11 · Inside delta bypassed, short off-time group
Current ratings in amperes;IEC source conditions1000 m altitude,40°C ambient. Keep installation/bypass state and exact duty header. Other operating conditions require supplier ratings. Models0735C~1220C require an external bypass contactor to achieve bypassed ratings.
| Source row | Model | 3.0-10:350 | 3.5-15:345 | 4.0-10:350 | 4.0-20:340 | 5.0-5:355 |
|---|---|---|---|---|---|---|
| 1 | 0024B | 36 | 30 | 29 | 24 | 24 |
| 2 | 0042B | 63 | 51 | 51 | 41 | 47 |
| 3 | 0052B | 78 | 62 | 59 | 51 | 51 |
Manual · PDF 11 · Inside delta bypassed, long off-time group
Current ratings in amperes;IEC source conditions1000 m altitude,40°C ambient. Keep installation/bypass state and exact duty header. Other operating conditions require supplier ratings. Models0735C~1220C require an external bypass contactor to achieve bypassed ratings.
| Source row | Model | 3.0-10:590 | 3.5-15:585 | 4.0-10:590 | 4.0-20:580 | 5.0-5:595 |
|---|---|---|---|---|---|---|
| 1 | 0064B | 96 | 93 | 90 | 75 | 80 |
| 2 | 0069B | 104 | 104 | 104 | 93 | 96 |
| 3 | 0105B | 158 | 129 | 126 | 102 | 114 |
| 4 | 0115B | 173 | 161 | 156 | 129 | 143 |
| 5 | 0135B | 203 | 194 | 189 | 155 | 173 |
| 6 | 0184B | 276 | 215 | 209 | 173 | 191 |
| 7 | 0200B | 300 | 255 | 248 | 207 | 225 |
| 8 | 0229B | 344 | 291 | 281 | 236 | 255 |
| 9 | 0250B | 375 | 366 | 345 | 300 | 303 |
| 10 | 0352B | 528 | 428 | 415 | 351 | 386 |
| 11 | 0397B | 596 | 484 | 466 | 393 | 433 |
| 12 | 0410B | 615 | 615 | 615 | 568 | 600 |
| 13 | 0550B | 825 | 789 | 758 | 640 | 694 |
| 14 | 0580B | 870 | 868 | 832 | 704 | 760 |
| 15 | 0835B | 1253 | 981 | 945 | 803 | 888 |
| 16 | 0940B | 1410 | 1104 | 1062 | 905 | 995 |
| 17 | 1070B | 1605 | 1425 | 1358 | 1178 | 1251 |
| 18 | 1230B | 1845 | 1731 | 1635 | 1439 | 1484 |
| 19 | 1250B | 1875 | 1875 | 1875 | 1733 | 1875 |
| 20 | 0735C | 1253 | 1098 | 1074 | 890 | 1043 |
| 21 | 0830C | 1410 | 1233 | 1205 | 1001 | 1164 |
| 22 | 1025C | 1815 | 1601 | 1550 | 1311 | 1473 |
| 23 | 1170C | 2145 | 1961 | 1878 | 1614 | 1755 |
| 24 | 1220C | 2430 | 2430 | 2424 | 1964 | 2430 |
Manual · PDF 12 · Inside delta non-bypassed
Current ratings in amperes;IEC source conditions1000 m altitude,40°C ambient. Keep installation/bypass state and exact duty header. Other operating conditions require supplier ratings.
| Source row | Model | 3.0-10:50-6 | 3.5-15:50-6 | 4.0-10:50-6 | 4.0-20:50-6 | 5.0-5:50-6 |
|---|---|---|---|---|---|---|
| 1 | 0735C | 1103 | 885 | 858 | 738 | 813 |
| 2 | 0830C | 1245 | 1001 | 968 | 836 | 914 |
| 3 | 1025C | 1538 | 1259 | 1208 | 1065 | 1127 |
| 4 | 1170C | 1755 | 1469 | 1401 | 1257 | 1293 |
| 5 | 1220C | 1830 | 1701 | 1664 | 1446 | 1613 |
Manual · PDF 12 · NEMA in-line bypassed
NEMA in-line installation;1000 m altitude,50°C ambient. Normal350%,30s,4starts/hour versusHeavy450%,30s,4starts/hour. Amperes andHP/voltage columns are distinct. Bypassed.
| Source row | Model | Normal350%,30s,4starts/hour / A | Normal350%,30s,4starts/hour / HP@240VAC | Normal350%,30s,4starts/hour / HP@480VAC | Normal350%,30s,4starts/hour / HP@600VAC | Heavy450%,30s,4starts/hour / A | Heavy450%,30s,4starts/hour / HP@240VAC | Heavy450%,30s,4starts/hour / HP@480VAC | Heavy450%,30s,4starts/hour / HP@600VAC |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 0024B | 17 | 5 | 10 | 15 | 14 | 3 | 10 | 10 |
| 2 | 0042B | 28 | 10 | 20 | 25 | 22 | 7.5 | 15 | 20 |
| 3 | 0052B | 35 | 10 | 25 | 30 | 28 | 10 | 20 | 25 |
| 4 | 0064B | 52 | 15 | 40 | 40 | 40 | 10 | 25 | 30 |
| 5 | 0069B | 59 | 20 | 40 | 50 | 46 | 15 | 30 | 40 |
| 6 | 0105B | 77 | 25 | 60 | 60 | 52 | 15 | 40 | 50 |
| 7 | 0115B | 81 | 30 | 60 | 75 | 65 | 20 | 50 | 60 |
| 8 | 0135B | 99 | 30 | 75 | 100 | 77 | 25 | 60 | 75 |
| 9 | 0184B | 124 | 40 | 100 | 100 | 96 | 30 | 75 | 75 |
| 10 | 0200B | 131 | 50 | 100 | 125 | 104 | 40 | 75 | 100 |
| 11 | 0229B | 156 | 60 | 125 | 150 | 124 | 40 | 100 | 100 |
| 12 | 0250B | 195 | 75 | 150 | 200 | 156 | 60 | 125 | 150 |
| 13 | 0352B | 240 | 75 | 200 | 200 | 180 | 60 | 150 | 150 |
| 14 | 0397B | 261 | 100 | 200 | 250 | 203 | 75 | 150 | 200 |
| 15 | 0410B | 377 | 150 | 300 | 350 | 302 | 100 | 250 | 300 |
| 16 | 0550B | 414 | 150 | 350 | 450 | 321 | 125 | 250 | 300 |
| 17 | 0580B | 477 | 200 | 400 | 500 | 361 | 150 | 300 | 350 |
| 18 | 0835B | 515 | 200 | 450 | 500 | 414 | 150 | 350 | 450 |
| 19 | 0940B | 590 | 200 | 500 | 600 | 480 | 200 | 400 | 500 |
| 20 | 1070B | 797 | 300 | 600 | 800 | 620 | 250 | 500 | 600 |
| 21 | 1230B | 985 | 400 | 800 | 1000 | 768 | 300 | 600 | 800 |
| 22 | 1250B | 1180 | 500 | 900 | 1200 | 904 | 350 | 700 | 900 |
| 23 | 0735C | 551 | 200 | 450 | 500 | 429 | 150 | 350 | 450 |
| 24 | 0830C | 634 | 250 | 500 | 600 | 493 | 200 | 400 | 500 |
| 25 | 1025C | 882 | 350 | 700 | 900 | 686 | 250 | 500 | 700 |
| 26 | 1170C | 1100 | 450 | 900 | 1100 | 864 | 350 | 700 | 900 |
| 27 | 1220C | 1320 | 500 | 1100 | 1300 | 1030 | 450 | 800 | 1000 |
Manual · PDF 13 · NEMA in-line non-bypassed
NEMA in-line installation;1000 m altitude,50°C ambient. Normal350%,30s,4starts/hour versusHeavy450%,30s,4starts/hour. Amperes andHP/voltage columns are distinct. Non-bypassed.
| Source row | Model | Normal350%,30s,4starts/hour / A | Normal350%,30s,4starts/hour / HP@240VAC | Normal350%,30s,4starts/hour / HP@480VAC | Normal350%,30s,4starts/hour / HP@600VAC | Heavy450%,30s,4starts/hour / A | Heavy450%,30s,4starts/hour / HP@240VAC | Heavy450%,30s,4starts/hour / HP@480VAC | Heavy450%,30s,4starts/hour / HP@600VAC |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 0735C | 480 | 200 | 400 | 500 | 382 | 150 | 300 | 400 |
| 2 | 0830C | 576 | 200 | 450 | 600 | 431 | 150 | 350 | 450 |
| 3 | 1025C | 722 | 300 | 600 | 700 | 590 | 200 | 500 | 600 |
| 4 | 1170C | 864 | 350 | 700 | 900 | 722 | 300 | 600 | 700 |
| 5 | 1220C | 966 | 400 | 800 | 1000 | 784 | 300 | 600 | 800 |
Manual · PDF 13 · Dimensions and weights0024B~0580B
Merged source cells expanded only across their visible row spans. A/B width,C/D height,E depth; original diagram governs geometry. Both units transcribed; no unit conversion recalculation.
| Source row | Model | Width A mm(inch) | Width B mm(inch) | Height C mm(inch) | Height D mm(inch) | Depth E mm(inch) | Weight kg(lb) |
|---|---|---|---|---|---|---|---|
| 1 | 0024B | 152 (6.0) | 92 (3.6) | 336 (13.2) | 307 (12.1) | 233 (9.2) | 4.8 (10.7) |
| 2 | 0042B | 152 (6.0) | 92 (3.6) | 336 (13.2) | 307 (12.1) | 233 (9.2) | 4.8 (10.7) |
| 3 | 0052B | 152 (6.0) | 92 (3.6) | 336 (13.2) | 307 (12.1) | 233 (9.2) | 4.9 (10.9) |
| 4 | 0064B | 152 (6.0) | 92 (3.6) | 336 (13.2) | 307 (12.1) | 233 (9.2) | 4.9 (10.9) |
| 5 | 0069B | 152 (6.0) | 92 (3.6) | 336 (13.2) | 307 (12.1) | 233 (9.2) | 4.9 (10.9) |
| 6 | 0105B | 152 (6.0) | 92 (3.6) | 336 (13.2) | 307 (12.1) | 233 (9.2) | 5.5 (12.1) |
| 7 | 0115B | 152 (6.0) | 92 (3.6) | 336 (13.2) | 307 (12.1) | 233 (9.2) | 5.5 (12.1) |
| 8 | 0135B | 152 (6.0) | 92 (3.6) | 336 (13.2) | 307 (12.1) | 233 (9.2) | 5.5 (12.1) |
| 9 | 0184B | 216 (8.5) | 180 (7.1) | 495 (19.5) | 450 (17.7) | 245 (9.6) | 12.7 (28.0) |
| 10 | 0200B | 216 (8.5) | 180 (7.1) | 495 (19.5) | 450 (17.7) | 245 (9.6) | 12.7 (28.0) |
| 11 | 0229B | 216 (8.5) | 180 (7.1) | 495 (19.5) | 450 (17.7) | 245 (9.6) | 12.7 (28.0) |
| 12 | 0250B | 216 (8.5) | 180 (7.1) | 495 (19.5) | 450 (17.7) | 245 (9.6) | 12.7 (28.0) |
| 13 | 0352B | 216 (8.5) | 180 (7.1) | 523 (20.6) | 450 (17.7) | 245 (9.6) | 15.5 (34.2) |
| 14 | 0397B | 216 (8.5) | 180 (7.1) | 523 (20.6) | 450 (17.7) | 245 (9.6) | 15.5 (34.2) |
| 15 | 0410B | 216 (8.5) | 180 (7.1) | 523 (20.6) | 450 (17.7) | 245 (9.6) | 15.5 (34.2) |
| 16 | 0550B | 216 (8.5) | 180 (7.1) | 523 (20.6) | 450 (17.7) | 245 (9.6) | 19.0 (41.9) |
| 17 | 0580B | 216 (8.5) | 180 (7.1) | 523 (20.6) | 450 (17.7) | 245 (9.6) | 19.0 (41.9) |
Manual · PDF 14 · Dimensions and weights0835B~1250B and0735C~1220C
Two separate merged dimension blocks; shared values expanded by visible row spans. Both printed units retained without conversion correction.
| Source row | Model | Width A mm(inch) | Width B mm(inch) | Height C mm(inch) | Height D mm(inch) | Depth E mm(inch) | Weight kg(lb) |
|---|---|---|---|---|---|---|---|
| 1 | 0835B | 447 (17.6) | 287 (11.3) | 618 (24.3) | 525 (20.7) | 310 (12.3) | 51.0 (112.4) |
| 2 | 0940B | 447 (17.6) | 287 (11.3) | 618 (24.3) | 525 (20.7) | 310 (12.3) | 51.0 (112.4) |
| 3 | 1070B | 447 (17.6) | 287 (11.3) | 618 (24.3) | 525 (20.7) | 310 (12.3) | 62.0 (136.7) |
| 4 | 1230B | 447 (17.6) | 287 (11.3) | 618 (24.3) | 525 (20.7) | 310 (12.3) | 63.0 (138.9) |
| 5 | 1250B | 447 (17.6) | 287 (11.3) | 618 (24.3) | 525 (20.7) | 310 (12.3) | 65.0 (143.3) |
| 6 | 0735C | 447 (17.6) | 287 (11.3) | 618 (24.3) | 525 (20.7) | 310 (12.3) | 47.0 (103.6) |
| 7 | 0830C | 447 (17.6) | 287 (11.3) | 618 (24.3) | 525 (20.7) | 310 (12.3) | 47.0 (103.6) |
| 8 | 1025C | 447 (17.6) | 287 (11.3) | 618 (24.3) | 525 (20.7) | 310 (12.3) | 58.0 (127.9) |
| 9 | 1170C | 447 (17.6) | 287 (11.3) | 618 (24.3) | 525 (20.7) | 310 (12.3) | 59.0 (130.1) |
| 10 | 1220C | 447 (17.6) | 287 (11.3) | 618 (24.3) | 525 (20.7) | 310 (12.3) | 61.0 (134.5) |
Manual · PDF 14 · Installation clearances
Physical diagram label associations; preserve strict greater-than sign. Clearance A/B/C/D are unrelated to dimension A/B/C/D above.
| Source row | Reference | Relationship | Source clearance |
|---|---|---|---|
| 1 | A | Between starters, vertical | >100 mm (3.9 inch) |
| 2 | B | Between starters, horizontal | >10 mm (0.4 inch) |
| 3 | C | Solid surfaces, above/below | >100 mm (3.9 inch) |
| 4 | D | Solid surfaces, sides | >10 mm (0.4 inch) |
Manual · PDF 16 · PFC legend
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Callout | Meaning |
|---|---|---|
| 1 | 1 | Soft starter |
| 2 | 2 | Programmable output (set = Run) |
| 3 | 3 | Power factor correction contactor |
| 4 | 4 | Power factor correction |
Manual · PDF 17 · IEC coordination0024B–0580B
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Nominal rating (A),300% FLC10s | SCR I²t (A²s) | Type1coordination480VAC65kA | Type2coordination690VAC65kA |
|---|---|---|---|---|---|
| 1 | 0024B | 24 | 1150 | 40NHG000B | 170M3010 |
| 2 | 0042B | 42 | 7200 | 63NHG000B | 170M3013 |
| 3 | 0052B | 52 | 7200 | 80NHG000B | 170M3013 |
| 4 | 0064B | 64 | 15000 | 100NHG000B | 170M3014 |
| 5 | 0069B | 69 | 15000 | 100NHG000B | 170M3014 |
| 6 | 0105B | 105 | 80000 | 160NHG00B | 170M3015 |
| 7 | 0115B | 115 | 80000 | 160NHG00B | 170M3015 |
| 8 | 0135B | 135 | 125000 | 160NHG00B | 170M3016 |
| 9 | 0184B | 184 | 320000 | 250NHG2B | 170M3020 |
| 10 | 0200B | 200 | 320000 | 250NHG2B | 170M3020 |
| 11 | 0229B | 229 | 320000 | 315NHG2B | 170M3020 |
| 12 | 0250B | 250 | 320000 | 315NHG2B | 170M3021 |
| 13 | 0352B | 352 | 202000 | 355NHG2B | 170M6009 |
| 14 | 0397B | 397 | 202000 | 400NHG2B | 170M6009 |
| 15 | 0410B | 410 | 320000 | 425NHG2B | 170M6010 |
| 16 | 0550B | 550 | 781000 | 630NHG3B | 170M6012 |
| 17 | 0580B | 580 | 781000 | 630NHG3B | 170M6012 |
Manual · PDF 17 · IEC coordination0835B–1250B bypassed
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Nominal rating (A),350% FLC30s | SCR I²t (A²s) | Type1coordination500VAC100kA | Type2coordination690VAC100kA |
|---|---|---|---|---|---|
| 1 | 0835B | 565 | 2530000 | 1000NHG4G | 170M6016 |
| 2 | 0940B | 638 | 2530000 | 1000NHG4G | 170M6017 |
| 3 | 1070B | 854 | 2530000 | 1200NHG4G | Not available |
| 4 | 1230B | 1055 | 3920000 | OFAA5GG1250 | Not available |
| 5 | 1250B | 1249 | 7220000 | OFAA5GG1250 | 170M6019 |
Manual · PDF 18 · IEC coordination0735C–1220C bypassed continuation
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Nominal rating (A),350% FLC30s | SCR I²t (A²s) | Type1coordination500VAC100kA | Type2coordination690VAC100kA |
|---|---|---|---|---|---|
| 1 | 0735C | 621 | 2530000 | 1000NHG4G | 170M6016 |
| 2 | 0830C | 699 | 2530000 | 1000NHG4G | 170M6017 |
| 3 | 1025C | 945 | 2530000 | OFAA5GG1250 | Not available |
| 4 | 1170C | 1178 | 3920000 | OFAA5GG1600 | Not available |
| 5 | 1220C | 1403 | 7220000 | OFAA5GG1600 | 170M6021 (at 500 VAC) |
Manual · PDF 18 · IEC coordination0735C–1220C continuous
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Nominal rating (A),350% FLC30s | SCR I²t (A²s) | Type1coordination500VAC100kA | Type2coordination690VAC100kA |
|---|---|---|---|---|---|
| 1 | 0735C | 535 | 2530000 | 1000NHG4G | 170M6016 |
| 2 | 0830C | 605 | 2530000 | 1000NHG4G | 170M6016 |
| 3 | 1025C | 775 | 2530000 | 1200NHG4G | 170M6017 |
| 4 | 1170C | 920 | 3920000 | OFAA5GG1250 | Not available |
| 5 | 1220C | 1044 | 7220000 | OFAA5GG1250 | 170M6019 |
Manual · PDF 18 · Standard fault shortcircuit0024B–0580B
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Nominalrating(A),300%FLC10s | 3cycleshortcircuitrating600VAC |
|---|---|---|---|
| 1 | 0024B | 24 | 5 kA |
| 2 | 0042B | 42 | 5 kA |
| 3 | 0052B | 52 | 10 kA |
| 4 | 0064B | 64 | 10 kA |
| 5 | 0069B | 69 | 10 kA |
| 6 | 0105B | 105 | 10 kA |
| 7 | 0115B | 120 | 10 kA |
| 8 | 0135B | 135 | 10 kA |
| 9 | 0184B | 184 | 18 kA |
| 10 | 0200B | 225 | 18 kA |
| 11 | 0229B | 229 | 18 kA |
| 12 | 0250B | 250 | 18 kA |
| 13 | 0352B | 352 | 18 kA |
| 14 | 0397B | 397 | 18 kA |
| 15 | 0410B | 410 | 30 kA |
| 16 | 0550B | 550 | 30 kA |
| 17 | 0580B | 580 | 30 kA |
Manual · PDF 19 · Standard fault shortcircuit Bmodels
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Nominal rating (A),350% FLC30s | Fault current at480or600VAC | Fuse maximum(A),ClassL at480or600VAC | Circuit breaker maximum(A),480VAConly |
|---|---|---|---|---|---|
| 1 | 0835B | 565 | 42 kA | 1350 | 1200 A |
| 2 | 0940B | 638 | 42 kA | 1350 | 1200 A |
| 3 | 1070B | 854 | 42 kA | 1350 | 1200 A |
| 4 | 1230B | 1055 | 85 kA | 2500 | 1200 A |
| 5 | 1250B | 1249 | 85 kA | 2500 | 1600 A |
Manual · PDF 19 · Standard fault shortcircuit Cmodels continuation
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Nominal rating (A),350% FLC30s | Fault current at480or600VAC | Fuse maximum(A),ClassL at480or600VAC | Circuit breaker maximum(A),480VAConly |
|---|---|---|---|---|---|
| 1 | 0735C | 621 | 42 kA | 1350 | 1200 A |
| 2 | 0830C | 699 | 42 kA | 1350 | 1200 A |
| 3 | 1025C | 945 | 42 kA | 1350 | 1200 A |
| 4 | 1170C | 1178 | 85 kA | 2500 | 1200 A |
| 5 | 1220C | 1403 | 85 kA | 2500 | 1600 A |
Manual · PDF 20 · High fault shortcircuit480VAC65kA
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Nominal rating (A),300% FLC10s | Circuit breaker options(rating,A),480VAC65kA | Fuse maximum(A),480VAC65kA | Fuse class |
|---|---|---|---|---|---|
| 1 | 0024B | 24 | HFD3030 (30 A) SELA36AT0060 (60 A) UTS150H-xxU-040 (40 A) 3VA140-6-* (40A) | 30 | Any (J, T, K-1, RK1, RK5) |
| 2 | 0042B | 42 | HFD3050 (50 A) SELA36AT0060 (60 A) UTS150H-xxU-050 (50 A) 3VA140-6-* (60A) | 50 | Any (J, T, K-1, RK1, RK5) |
| 3 | 0052B | 52 | HFD3060 (60 A) SELA36AT0060 (60 A) UTS150H-xxU-060 (60 A) 3VA140-6-* (70A) | 60 | Any (J, T, K-1, RK1, RK5) |
| 4 | 0064B | 64 | HFD3100 (100 A) SELA36AT0150 (150 A) UTS150H-xxU-100 (100 A) 3VA140-6-* (100 A) | 80 | Any (J, T, K-1, RK1, RK5) |
| 5 | 0069B | 69 | HFD3100 (100 A) SELA36AT0150 (150 A) UTS150H-xxU-100 (100 A) 3VA140-6-* (100 A) | 80 | Any (J, T, K-1, RK1, RK5) |
| 6 | 0105B | 105 | HFD3125 (125 A) SELA36AT0150 (150 A) UTS150H-xxU-125 (125 A) 3VA225-6-* (150 A) | 125 | J, T, K-1, RK1 |
| 7 | 0115B | 115 | HFD3125 (125 A) SELA36AT0150 (150 A) UTS150H-xxU-125 (125 A) 3VA225-6-* (150 A) | 125 | J, T, K-1, RK1 |
| 8 | 0135B | 135 | HFD3150 (150 A) SELA36AT0150 (150 A) UTS150H-xxU-150 (150 A) 3VA225-6-* (250 A) | 150 | J, T, K-1, RK1 |
Manual · PDF 21 · High fault shortcircuit480VAC65kA continuation
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Nominal rating (A),300% FLC10s | Circuit breaker options(rating,A),480VAC65kA | Fuse maximum(A),480VAC65kA | Fuse class |
|---|---|---|---|---|---|
| 1 | 0184B | 184 | HJD3250 (250 A) SFLA36AT0250 (250 A) UTS250H-xxU-250 (250 A) 3VA225-6-* (250 A) | 200 | J, T |
| 2 | 0200B | 200 | HJD3250 (250 A) SFLA36AT0250 (250 A) UTS250H-xxU-250 (250 A) 3VA225-6-* (250 A) | 225 | J, T |
| 3 | 0229B | 229 | HJD3250 (250 A) SFLA36AT0250 (250 A) UTS250H-xxU-250 (250 A) 3VA340-6-* (400 A) | 250 | J, T |
| 4 | 0250B | 250 | HKD3300 (300 A) SGLA36AT0400 (400 A) UTS400H-xxU-300 (300 A) 3VA340-6-* (400 A) | 300 | J, T |
| 5 | 0352B | 352 | HLD3400 (400 A) SGLA36AT0600 (600 A) UTS400H-xxU-400 (400 A) HMD63B800 (800 A) | 400 | Any (J, T, K-1, RK1, RK5) |
| 6 | 0397B | 397 | HLD3400 (400 A) SGLA36AT0600 (600 A) UTS400H-xxU-400 (400 A) HND63B900 (900 A) | 450 | Any (J, T, K-1, RK1, RK5) |
| 7 | 0410B | 410 | HLD3600 (600 A) SGLA36AT0600 (600 A) UTS600H-xxU-600 (600 A) HND63B100 (1000 A) | 450 | Any (J, T, K-1, RK1, RK5) |
| 8 | 0550B | 550 | HLD3600 (600 A) SGLA36AT0600 (600 A) UTS800H-NGx-800 (800 A) HND63B120 (1200 A) | 600 | Any (J, T, K-1, RK1, RK5) |
| 9 | 0580B | 580 | HLD3600 (600 A) SGLA36AT0600 (600 A) UTS800H-NGx-800 (800 A) HND63B120 (1200 A) | 600 | Any (J, T, K-1, RK1, RK5) |
Manual · PDF 22 · High fault shortcircuit600VAC
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Nominalrating(A),350%FLC30s | Circuitbreakermax(A),600VAC50kA | Fusemax(A),600VAC100kA | Fuseclass |
|---|---|---|---|---|---|
| 1 | 0024B | 18 | UTS150L-xxU-040 (40 A) | 40 | Any (J, T, K-1 RK1, RK5) |
| 2 | 0042B | 30 | UTS150L-xxU-060 (60 A) | 60 | Any (J, T, K-1 RK1, RK5) |
| 3 | 0052B | 38 | UTS150L-xxU-070 (70 A) | 70 | Any (J, T, K-1 RK1, RK5) |
| 4 | 0064B | 52 | UTS150L-xxU-100 (100 A) | 100 | Any (J, T, K-1 RK1, RK5) |
| 5 | 0069B | 64 | UTS150L-xxU-125 (125 A) | 125 | Any (J, T, K-1 RK1, RK5) |
| 6 | 0105B | 70 | UTS150L-xxU-150 (150 A) | 200 | Any (J, T, K-1 RK1, RK5) |
| 7 | 0115B | 88 | UTS150L-xxU-150 (150 A) | 250 | Any (J, T, K-1 RK1, RK5) |
| 8 | 0135B | 105 | UTS250L-xxU-250 (250 A) | 300 | Any (J, T, K-1 RK1, RK5) |
| 9 | 0184B | 120 | UTS400L-xxU-300 (300 A) | 300 | Any (J, T, K-1 RK1, RK5) |
| 10 | 0200B | 144 | UTS400L-xxU-350 (350 A) | 350 | Any (J, T, K-1 RK1, RK5) |
| 11 | 0229B | 164 | UTS400L-xxU-400 (400 A) | 400 | Any (J, T, K-1 RK1, RK5) |
| 12 | 0250B | 212 | UTS800L-NGx-600 (600 A) | 500 | L |
| 13 | 0352B | 247 | UTS800L-NGx-800 (800 A) | 700 | L |
| 14 | 0397B | 279 | UTS1200P-NGx-1000 (900 A1) | 700 | L |
| 15 | 0410B | 404 | UTS1200P-NGx-1000 (1000 A) | 800 | L |
| 16 | 0550B | 449 | UTS1200P-NGx-1200 (1200 A) | 900 | L |
| 17 | 0580B | 495 | UTS1200P-NGx-1200 (1200 A) | 1000 | L |
Manual · PDF 22 · High fault shortcircuit0835B480VAC
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Nominal rating (A),350% FLC30s | Fault current,480VAC | Circuit breaker options(rating,Amax),480VAC | Fuse maximum(A),ClassL480VAC |
|---|---|---|---|---|---|
| 1 | 0835B | 565 | 65 kA | UTS600H-xxU-600 (600A) UTS800H-NGx-800 (800A) UTS1200H-NGx-1200 (1200A) | 1350 |
| 2 | 0835B | 565 | 100 kA | UTS600L-xxU-600 (600A) UTS800L-NGx-800 (800A) UTS1200L-NGx-1200 (1200A) | 1350 |
Manual · PDF 23 · High fault shortcircuit Bmodels480VAC continuation
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Nominal rating (A),350% FLC30s | Fault current,480VAC | Circuit breaker options(rating,Amax),480VAC | Fuse maximum(A),ClassL480VAC |
|---|---|---|---|---|---|
| 1 | 0940 | 638 | 65 kA | UTS600H-xxU-600 (600A) UTS800H-NGx-800 (800A) UTS1200H-NGx-1200 (1200A) | 1350 |
| 2 | 0940 | 638 | 100 kA | UTS600L-xxU-600 (600A) UTS800L-NGx-800 (800A) UTS1200L-NGx-1200 (1200A) | 1350 |
| 3 | 1070B | 854 | 65 kA | UTS600H-xxU-600 (600A) UTS800H-NGx-800 (800A) UTS1200H-NGx-1200 (1200A) | 1350 |
| 4 | 1070B | 854 | 100 kA | UTS600L-xxU-600 (600A) UTS800L-NGx-800 (800A) UTS1200L-NGx-1200 (1200A) | 1350 |
| 5 | 1230B | 1055 | 65kA | HPD63B160 (1600A) | 2500 |
| 6 | 1230B | 1055 | 100kA | UTS1200L-NGx-1200 (1200A) CPD63B160 (1600A) | 2500 |
| 7 | 1250B | 1249 | 65kA | HPD63B160 (1600A) | 2500 |
| 8 | 1250B | 1249 | 100kA | UTS1200L-NGx-1200 (1200A) CPD63B160 (1600A) | 2500 |
Manual · PDF 23 · High fault shortcircuit Cmodels480VAC
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Nominal rating (A),350% FLC30s | Fault current,480VAC | Circuit breaker options(rating,Amax),480VAC | Fuse maximum(A),ClassL480VAC |
|---|---|---|---|---|---|
| 1 | 0735C | 621 | 65 kA | UTS600H-xxU-600 (600A) UTS800H-NGx-800 (800A) UTS1200H-NGx-1200 (1200A) | 1350 |
| 2 | 0735C | 621 | 100 kA | UTS600L-xxU-600 (600A) UTS800L-NGx-800 (800A) UTS1200L-NGx-1200 (1200A) | 1350 |
| 3 | 0830C | 699 | 65 kA | UTS600H-xxU-600 (600A) UTS800H-NGx-800 (800A) UTS1200H-NGx-1200 (1200A) | 1350 |
| 4 | 0830C | 699 | 100 kA | UTS600L-xxU-600 (600A) UTS800L-NGx-800 (800A) UTS1200L-NGx-1200 (1200A) | 1350 |
| 5 | 1025C | 945 | 65 kA | UTS600H-xxU-600 (600A) UTS800H-NGx-800 (800A) UTS1200H-NGx-1200 (1200A) | 1350 |
| 6 | 1025C | 945 | 100 kA | UTS600L-xxU-600 (600A) UTS800L-NGx-800 (800A) UTS1200L-NGx-1200 (1200A) | 1350 |
| 7 | 1170C | 1178 | 65 kA | HPD63B160 (1600A) | 2500 |
| 8 | 1170C | 1178 | 100 kA | UTS1200L-NGx-1200 (1200A) CPD63B160 (1600A) | 2500 |
| 9 | 1220C | 1403 | 65 kA | HPD63B160 (1600A) | 2500 |
| 10 | 1220C | 1403 | 100 kA | UTS1200L-NGx-1200 (1200A) CPD63B160 (1600A) | 2500 |
Manual · PDF 24 · High fault shortcircuit600VAC
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Nominalrating(A),350%FLC30s | Circuitbreakeroptionsmax(A),600VAC50kA | Circuitbreakermax(A),600VAC65kA | Fusemax(A),ClassL600VAC100kA |
|---|---|---|---|---|---|
| 1 | 0835B | 565 | HPD63B160 (1600A) UTS1200P‐NGx‐1200 (1200A) | CPD63B160 (1600A) | 1350 |
| 2 | 0940B | 638 | HPD63B160 (1600A) UTS1200P‐NGx‐1200 (1200A) | CPD63B160 (1600A) | 1350 |
| 3 | 1070B | 854 | HPD63B160 (1600A) UTS1200P‐NGx‐1200 (1200A) | CPD63B160 (1600A) | 1350 |
| 4 | 1230B | 1055 | HPD63B160 (1600A) UTS1200P‐NGx‐1200 (1200A) | CPD63B160 (1600A) | 2500 |
| 5 | 1250B | 1249 | HPD63B160 (1600A) UTS1200P‐NGx‐1200 (1200A) | CPD63B160 (1600A) | 2500 |
| 6 | 0735C | 621 | HPD63B160 (1600A) UTS1200P‐NGx‐1200 (1200A) | CPD63B160 (1600A) | 1350 |
| 7 | 0830C | 699 | HPD63B160 (1600A) UTS1200P‐NGx‐1200 (1200A) | CPD63B160 (1600A) | 1350 |
| 8 | 1025C | 945 | HPD63B160 (1600A) UTS1200P‐NGx‐1200 (1200A) | CPD63B160 (1600A) | 1350 |
| 9 | 1170C | 1178 | HPD63B160 (1600A) UTS1200P‐NGx‐1200 (1200A) | CPD63B160 (1600A) | 2500 |
| 10 | 1220C | 1403 | HPD63B160 (1600A) UTS1200P‐NGx‐1200 (1200A) | CPD63B160 (1600A) | 2500 |
Manual · PDF 25 · Electrical and environmental specifications
Labels include source heading/terminal context to avoid association loss. Original tolerances, inequalities and derating clauses retained. Directive/standards are supplier statements only.
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | Supply / mains xxxxX-V5 (L1,L2,L3) | 200~525 VAC (±10%) |
| 2 | Supply / mains xxxxX-V7 (L1,L2,L3) | 380~690 VAC (±10%) |
| 3 | Control xxxxX-xx-C1 (A1,A2) | 110~120 VAC (+10%/-15%),600 mA |
| 4 | Control xxxxX-xx-C1 (A2,A3) | 220~240 VAC (+10%/-15%),600 mA |
| 5 | Control xxxxX-xx-C2 (A1,A2) | 24 VAC/VDC (±20%),2.8 A |
| 6 | Mains frequency | 50 Hz~60 Hz (±5 Hz) |
| 7 | Rated insulation voltage | 690 VAC |
| 8 | Rated impulse withstand voltage | 6 kV |
| 9 | Form designation | Bypassed or continuous, semiconductor motor starter form1 |
| 10 | Short circuit / semiconductor fuses | Type2 |
| 11 | Short circuit / HRC fuses | Type1 |
| 12 | Electromagnetic capability heading | compliant with EU Directive2014/35/EU |
| 13 | EMC Immunity | IEC60947-4-2 |
| 14 | EMC Emissions | IEC60947-4-2 Class B |
| 15 | Input rating | Active24 VDC,8 mA approx |
| 16 | Motor thermistor (B4,B5) | Trip >3.6 kΩ,reset <1.6 kΩ |
| 17 | Relay outputs | 10 A@250 VAC resistive,5A@250 VAC AC15 pf0.3 |
| 18 | Main contactor (33,34) | Normally open |
| 19 | Bypass contactor (03,04) | Normally open |
| 20 | Relay output A (41,42,44) | Changeover |
| 21 | Relay output B (53,54) | Normally open |
| 22 | Analog output (21,22) / maximum load | 600 Ω (12 VDC@20 mA) |
| 23 | Analog output (21,22) / accuracy | ±5% |
| 24 | Operating temperature | -10°C~60°C,above40°C with derating |
| 25 | Storage temperature | -25°C~+60°C |
| 26 | Operating altitude | 0~1000 m,above1000 m with derating |
| 27 | Humidity | 5%~95% Relative Humidity |
| 28 | Pollution degree | Pollution Degree3 |
| 29 | Vibration | IEC60068-2-6 |
| 30 | Protection0024B~0135B | IP20 |
| 31 | Protection0184B~1250B | IP00 |
| 32 | Protection0735C~1220C | IP00 |
Manual · PDF 26 · Heat dissipation and internal bypass contact life
Heat dissipation depends on operation and model group. Lifetime is source statement, not warranty or present condition.
| Source row | Source label/context | Source value |
|---|---|---|
| 1 | During Start | 4.5 watts per ampere |
| 2 | During Run(Bypassed)0024B~0052B | ≤35 watts approx |
| 3 | During Run(Bypassed)0064B~0135B | ≤50 watts approx |
| 4 | During Run(Bypassed)0184B~0250B | ≤120 watts approx |
| 5 | During Run(Bypassed)0352B~0580B | ≤140 watts approx |
| 6 | During Run(Bypassed)0835B~1250B | ≤180 watts approx |
| 7 | During Run(Non-bypassed)0735C~1220C | 4.5 watts per ampere |
| 8 | Operational life(internal bypass contacts) | 100000 operations |
Manual · PDF 28 · Input terminal legend
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Terminal | Function |
|---|---|---|
| 1 | B4, B5 | Motor thermistor input |
| 2 | 10, 11 | Reset input |
| 3 | 11, 12 | Start/stop input |
| 4 | 13, 14 | Programmable input A (default = Input Trip (N/O)) |
| 5 | 13, 15 | Programmable input B (default = Input Trip (N/O)) |
| 6 | [USB symbol] | USB port |
Manual · PDF 29 · Output terminal legend
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Terminal | Function |
|---|---|---|
| 1 | 21, 22 | Analog output |
| 2 | 33, 34 | Main contactor output |
| 3 | 41, 42, 44 | Relay output A (default = Run) |
| 4 | 53, 54 | Relay output B (default = Run) |
| 5 | 03, 04 | Bypass contactor output |
Manual · PDF 30 · Maincontactor legend
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Symbol | Meaning |
|---|---|---|
| 1 | F1 | Fuses |
| 2 | K1 | Main contactor |
Manual · PDF 30 · Shunttrip circuitbreaker legend
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Symbol | Meaning |
|---|---|---|
| 1 | Q1 | Circuit breaker |
Manual · PDF 32 · Exampleconnectors
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Exampleconnector aluminiumcable | Exampleconnector coppercable |
|---|---|---|---|
| 1 | 0184B | 61162 | 60150 |
| 2 | 0200B | 61165 | 60156 |
| 3 | 0229B | 61171 | 60165 |
| 4 | 0250B | 61171 | 60165 |
| 5 | 0352B | 61162 | 60150 |
| 6 | 0397B | 61165 | 60156 |
| 7 | 0410B | 61165 | 60162 |
Manual · PDF 33 · Exampleconnectors continuation
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Model | Exampleconnector aluminiumcable | Exampleconnector coppercable |
|---|---|---|---|
| 1 | 0550B | 61178 | 60171 |
| 2 | 0580B | 61178 | 60171 |
Manual · PDF 33 · Inline internallybypassed legend
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Symbol | Meaning |
|---|---|---|
| 1 | K1 | Main contactor (strongly recommended) |
| 2 | F1 | Fuses or circuit breaker |
| 3 | 33, 34 | Main contactor output |
Manual · PDF 34 · Inline externallybypassed legend
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Symbol | Meaning |
|---|---|---|
| 1 | K1 | Main contactor (strongly recommended) |
| 2 | K2 | Bypass contactor |
| 3 | F1 | Fuses or circuit breaker |
| 4 | 33, 34 | Main contactor output |
| 5 | 03, 04 | Bypass contactor output |
Manual · PDF 34 · Insidedelta internallybypassed legend
Exact source edition and voltage/duty/fault-current/configuration context required; merged cells expanded only within their physically printed span. Not a current certification or substitute component approval.
| Source row | Symbol | Meaning |
|---|---|---|
| 1 | K1 | Main contactor |
| 2 | F1 | Fuses or circuit breaker |
| 3 | 33, 34 | Main contactor output |
Manual · PDF 35 · Inside-delta externally bypassed legend
Historical supplier source instructions. Suggested application settings require application-specific adjustment; not guaranteed commissioning values. Labels identify source diagram only, not reconstructed wiring geometry.
| Source row | Callout / terminal | Meaning |
|---|---|---|
| 1 | K1 | Main contactor |
| 2 | K2 | Bypass contactor (external) |
| 3 | F1 | Fuses or circuit breaker |
| 4 | 33, 34 | Main contactor output |
| 5 | 03, 04 | Bypass contactor output |
Manual · PDF 36 · Internally bypassed diagram callouts
Historical supplier source instructions. Suggested application settings require application-specific adjustment; not guaranteed commissioning values. Labels identify source diagram only, not reconstructed wiring geometry.
| Source row | Callout / terminal | Meaning |
|---|---|---|
| 1 | 1 | Three-phase supply |
| 2 | 2 | Motor |
| 3 | 3 | Control voltage (soft starter) |
| 4 | 4 | Digital inputs |
| 5 | 5 | Motor thermistor input |
| 6 | 6 | Relay outputs |
| 7 | 7 | Analog output |
| 8 | 8 | Control voltage (external equipment) |
| 9 | 9 | Pilot lamps |
| 10 | 10 | Communications / Smart card expansion port |
Manual · PDF 36 · Internally bypassed terminal legend
Historical supplier source instructions. Suggested application settings require application-specific adjustment; not guaranteed commissioning values. Labels identify source diagram only, not reconstructed wiring geometry.
| Source row | Callout / terminal | Meaning |
|---|---|---|
| 1 | K1 | Main contactor |
| 2 | F1 | Fuses or circuit breaker |
| 3 | 10, 11 (S1) | Reset |
| 4 | 11, 12 (S2) | Start/Stop |
| 5 | 13, 14 | Programmable input A (default = Input Trip (N/O)) |
| 6 | 13, 15 | Programmable input B (default = Input Trip (N/O)) |
| 7 | B4, B5 | Motor thermistor input |
| 8 | 33, 34 | Main contactor output |
| 9 | 41, 42, 44 | Relay output A (default = Run) |
| 10 | 53, 54 | Relay output B (default = Run) |
| 11 | 21, 22 | Analog output |
Manual · PDF 38 · Externally bypassed diagram callouts
Historical supplier source instructions. Suggested application settings require application-specific adjustment; not guaranteed commissioning values. Labels identify source diagram only, not reconstructed wiring geometry.
| Source row | Callout / terminal | Meaning |
|---|---|---|
| 1 | 1 | Three-phase supply |
| 2 | 2 | Motor |
| 3 | 3 | Control voltage (soft starter) |
| 4 | 4 | Digital inputs |
| 5 | 5 | Motor thermistor input |
| 6 | 6 | Relay outputs |
| 7 | 7 | Analog output |
| 8 | 8 | Control voltage (external equipment) |
| 9 | 9 | Pilot lamps |
| 10 | 10 | Communications / Smart card expansion port |
Manual · PDF 38 · Externally bypassed terminal legend
Historical supplier source instructions. Suggested application settings require application-specific adjustment; not guaranteed commissioning values. Labels identify source diagram only, not reconstructed wiring geometry.
| Source row | Callout / terminal | Meaning |
|---|---|---|
| 1 | K1 | Main contactor |
| 2 | K2 | Bypass contactor (external) |
| 3 | F1 | Fuses or circuit breaker |
| 4 | 10, 11 (S1) | Reset |
| 5 | 11, 12 (S2) | Start/Stop |
| 6 | 13, 14 | Programmable input A (default = Input Trip (N/O)) |
| 7 | 13, 15 | Programmable input B (default = Input Trip (N/O)) |
| 8 | B4, B5 | Motor thermistor input |
| 9 | 33, 34 | Main contactor output |
| 10 | 41, 42, 44 | Relay output A (default = Run) |
| 11 | 53, 54 | Relay output B (default = Run) |
| 12 | 03, 04 | Bypass contactor output |
| 13 | 21, 22 | Analog output |
Manual · PDF 38 · Quick setup suggested settings
Historical supplier source instructions. Suggested application settings require application-specific adjustment; not guaranteed commissioning values. Labels identify source diagram only, not reconstructed wiring geometry.
| Source row | Application | Start Mode | Start Ramp Time(seconds) | Initial Current(%) | Current Limit(%) | Adaptive Start Profile | Stop Mode | Stop Time(seconds) | Adaptive Stop Profile |
|---|---|---|---|---|---|---|---|---|---|
| 1 | Pump Centrifugal | Adaptive Control | 10 | 200 | 500 | Early accel. | Adaptive Control | 15 | Late decel. |
| 2 | Pump bore | Adaptive Control | 3 | 200 | 500 | Early accel. | Adaptive Control | 3 | Late decel. |
| 3 | Pump Hydraulic | Constant Current | 2 | 200 | 350 | n/a | Coast To Stop | n/a | n/a |
| 4 | Fan Damped | Constant Current | 2 | 200 | 350 | n/a | Coast To Stop | n/a | n/a |
| 5 | Fan Undamped | Constant Current | 2 | 200 | 450 | n/a | Coast To Stop | n/a | n/a |
| 6 | Compressor Screw | Constant Current | 2 | 200 | 400 | n/a | Coast To Stop | n/a | n/a |
| 7 | Compressor Recip | Constant Current | 2 | 200 | 450 | n/a | Coast To Stop | n/a | n/a |
| 8 | Conveyor | Constant Current | 5 | 200 | 450 | n/a | Coast To Stop | n/a | n/a |
| 9 | Bow thruster | Constant Current | 5 | 100 | 400 | n/a | Coast To Stop | n/a | n/a |
| 10 | Bandsaw | Constant Current | 2 | 200 | 450 | n/a | Coast To Stop | n/a | n/a |
Manual · PDF 41 · USB file locations and formats
Historical supplier source instructions. Suggested application settings require application-specific adjustment; not guaranteed commissioning values. Labels identify source diagram only, not reconstructed wiring geometry.
| Source row | Function | File location |
|---|---|---|
| 1 | Save Parameters and Logs | The starter will create a directory at the top level of the USB drive, named with the soft starter's serial number. The event log and parameter settings are saved as individual CSV files, and the soft starter's software and system information are saved to a text file. |
| 2 | Save Master Parameters | The starter will create a file called Master_Parameters.par, in the top level of the USB drive. |
| 3 | Load Master Parameters | The starter will load the file Master_Parameters.par from the top level of the USB drive. This file can be created or edited using the soft starter management software. |
| 4 | Load Custom Message | The starter will load the files Custom_Message_A.txt and Custom_Message_B.txt from the top level of the USB drive. |
Manual · PDF 43 · Digital I/O state inputs
Printed legend mapped to source callouts; no inferred wiring topology.
| Source row | Callout | Terminal and function |
|---|---|---|
| 1 | 1 | 10, 11: Reset input |
| 2 | 2 | 11, 12: Start/stop input |
| 3 | 3 | 13, 14: Programmable input A |
| 4 | 4 | 13, 15: Programmable input B |
Manual · PDF 43 · Digital I/O state outputs
Printed legend mapped to source callouts; no inferred wiring topology.
| Source row | Callout | Terminal and function |
|---|---|---|
| 1 | 5 | 33, 34: Main contactor output |
| 2 | 6 | 41, 42, 44: Relay output A |
| 3 | 7 | 53, 54: Relay output B |
Manual · PDF 46 · Keypad controls
Historical supplier source instructions. Suggested application settings require application-specific adjustment; not guaranteed commissioning values. Labels identify source diagram only, not reconstructed wiring geometry.
| Source row | Callout / terminal | Meaning |
|---|---|---|
| 1 | 1 | Four-line display for status and programming details. |
| 2 | 2 | Status LEDs |
| 3 | 3 | Menu navigation buttons: RESET/EXIT: Exit the menu or parameter, or cancel a parameter change. On the local keypad, this button also resets a trip. MENU/ENTER: Enter a menu or parameter, or save a parameter change. ▲ ▼: Scroll to the next or previous menu or parameter, change the setting of the current parameter or scroll through the status screens. |
| 4 | 4 | Shortcut to the command source menu in Setup Tools. |
| 5 | 5 | Soft starter local control buttons |
| 6 | 6 | Shortcut buttons for quick access to common tasks. LOGS: Open the Logs Menu. GRAPHS: Select which graph to view, or pause/restart the graph (hold longer than 0.5 seconds) TOOLS: Open the Setup Tools. |
Manual · PDF 47 · Starter status LEDs
Historical supplier source instructions. Suggested application settings require application-specific adjustment; not guaranteed commissioning values. Labels identify source diagram only, not reconstructed wiring geometry.
| Source row | LED name | On | Flashing |
|---|---|---|---|
| 1 | Ready | The motor is stopped and the starter is ready to start. | The motor is stopped and the starter is not ready to start: waiting for the Restart Delay (parameter 5P) the thermal models indicate the starter and/or motor are too hot to start safely the reset input (10, 11) is open |
| 2 | Run | The motor is in run state (receiving full voltage). | The motor is starting or stopping. |
| 3 | Trip | The starter has tripped. | The starter is in warning state. |
| 4 | Local | The starter is being controlled via a remote keypad. | – |
Manual · PDF 51 · Typical control methods
Historical supplier source instructions. Suggested application settings require application-specific adjustment; not guaranteed commissioning values. Labels identify source diagram only, not reconstructed wiring geometry.
| Source row | Application | Start Mode | Start Ramp Time(seconds) | Initial Current(%FLC) | Current Limit(%FLC) | Stop Mode | Stop Time(seconds) |
|---|---|---|---|---|---|---|---|
| 1 | Bow thruster | Constant Current | 5 | 100 | 400 | Coast To Stop | n/a |
| 2 | Centrifuge (Separator) | Constant Current | 1 | 200 | 450 | Coast To Stop | n/a |
| 3 | Chipper | Constant Current | 1 | 200 | 450 | Coast To Stop | n/a |
| 4 | Compressor - reciprocating - loaded | Constant Current | 1 | 200 | 450 | Coast To Stop | n/a |
| 5 | Compressor - reciprocating - unloaded | Constant Current | 1 | 200 | 400 | Coast To Stop | n/a |
| 6 | Compressor - screw - loaded | Constant Current | 1 | 200 | 400 | Coast To Stop | n/a |
| 7 | Compressor - screw - unloaded | Constant Current | 1 | 200 | 350 | Coast To Stop | n/a |
| 8 | Conveyor - horizontal | Constant Current | 5 | 200 | 400 | TVR Soft Stop | 10 |
| 9 | Conveyor - inclined | Constant Current | 2 | 200 | 450 | Coast To Stop | n/a |
| 10 | Conveyor - vertical (bucket) | Constant Current | 2 | 200 | 450 | Coast To Stop | n/a |
| 11 | Crusher - cone | Constant Current | 1 | 200 | 350 | Coast To Stop | n/a |
| 12 | Crusher - jaw | Constant Current | 1 | 200 | 450 | Coast To Stop | n/a |
| 13 | Crusher - rotary | Constant Current | 1 | 200 | 400 | Coast To Stop | n/a |
| 14 | Debarker | Constant Current | 1 | 200 | 350 | Coast To Stop | n/a |
| 15 | Fan - axial (damped) | Constant Current | 1 | 200 | 350 | Coast To Stop | n/a |
| 16 | Fan - axial (undamped) | Constant Current | 1 | 200 | 450 | Coast To Stop | n/a |
| 17 | Fan - centrifugal (damped) | Constant Current | 1 | 200 | 350 | Coast To Stop | n/a |
| 18 | Fan - centrifugal (undamped) | Constant Current | 1 | 200 | 450 | Coast To Stop | n/a |
| 19 | Fan - high pressure | Constant Current | 1 | 200 | 450 | Coast To Stop | n/a |
| 20 | Mill - ball | Constant Current | 1 | 200 | 450 | Coast To Stop | n/a |
| 21 | Mill - hammer | Constant Current | 1 | 200 | 450 | Coast To Stop | n/a |
| 22 | Pump - bore | Adaptive Control (Early accel.) | 3 | n/a | 500 | Adaptive Control (Late decel.) | 3 |
| 23 | Pump - centrifugal | Adaptive Control (Early accel.) | 10 | n/a | 500 | Adaptive Control (Late decel.) | 15 |
Manual · PDF 52 · Typical control methods continuation
Typical control methods continuation
Historical supplier source instructions. Suggested application settings require application-specific adjustment; not guaranteed commissioning values. Labels identify source diagram only, not reconstructed wiring geometry.
| Source row | Application | Start Mode | Start Ramp Time(seconds) | Initial Current(%FLC) | Current Limit(%FLC) | Stop Mode | Stop Time(seconds) |
|---|---|---|---|---|---|---|---|
| 1 | Pump - Hydraulic | Constant Current | 2 | 200 | 350 | Coast To Stop | n/a |
| 2 | Pump - positive displacement | Adaptive Control (Const. accel.) | 10 | n/a | 400 | Adaptive Control (Const. decel.) | 10 |
| 3 | Pump - submersible | Adaptive Control (Early accel.) | 5 | n/a | 500 | Adaptive Control (Late decel.) | 5 |
| 4 | Saw - bandsaw | Constant Current | 1 | 200 | 450 | Coast To Stop | n/a |
| 5 | Saw - circular | Constant Current | 1 | 200 | 350 | Coast To Stop | n/a |
| 6 | Shredder | Constant Current | 1 | 200 | 450 | Coast To Stop | n/a |
Manual · PDF 56 · Adaptive stop profile applications
Historical supplier instructions. Legend labels only; original diagram authoritative for wiring. Installation conditions and source warnings remain mandatory context.
| Source row | Adaptive Stop Profile | Application |
|---|---|---|
| 1 | Late Deceleration | High head systems where even a small decrease in motor/pump speed results in a rapid transition between forward flow and reverse flow. |
| 2 | Constant Deceleration | Low to medium head, high flow applications where the fluid has high momentum. |
| 3 | Early Deceleration | Open pump systems where fluid must drain back through the pump without driving the pump in reverse. |
Manual · PDF 57 · Soft brake diagram legend
Historical supplier instructions. Legend labels only; original diagram authoritative for wiring. Installation conditions and source warnings remain mandatory context.
| Source row | Callout | Meaning |
|---|---|---|
| 1 | 1 | Three-phase supply |
| 2 | 2 | Motor terminals |
| 3 | 3 | Relay output A |
| 4 | 4 | K1/K2 coil supply |
| 5 | 5 | Programmable input A |
Manual · PDF 57 · Soft brake contactor and sensor legend
Historical supplier instructions. Legend labels only; original diagram authoritative for wiring. Installation conditions and source warnings remain mandatory context.
| Source row | Label | Meaning |
|---|---|---|
| 1 | K1 | Line contactor (Run) |
| 2 | K2 | Line contactor (Brake) |
| 3 | A2 | Zero speed sensor |
Manual · PDF 58 · Pump clean sequence legend 1–4
Historical supplier instructions. Legend labels only; original diagram authoritative for wiring. Installation conditions and source warnings remain mandatory context.
| Source row | Callout | Meaning |
|---|---|---|
| 1 | 1 | Reverse Torque (parameter 11A) |
| 2 | 2 | Reverse Time (parameter 11B) |
| 3 | 3 | Forward Current Limit (parameter 11C) |
| 4 | 4 | Forward Time (parameter 11D) |
Manual · PDF 58 · Pump clean sequence legend 5–8
Historical supplier instructions. Legend labels only; original diagram authoritative for wiring. Installation conditions and source warnings remain mandatory context.
| Source row | Callout | Meaning |
|---|---|---|
| 1 | 5 | Pump Stop Time (parameter 11F) |
| 2 | 6 | Cleaning cycle |
| 3 | 7 | Pump Clean Cycles (parameter 11G) |
| 4 | 8 | Programmed soft start |
Manual · PDF 59 · Reverse operation diagram legend
Historical supplier instructions. Legend labels only; original diagram authoritative for wiring. Installation conditions and source warnings remain mandatory context.
| Source row | Callout | Meaning |
|---|---|---|
| 1 | 1 | Three-phase supply |
| 2 | 2 | Motor terminals |
| 3 | 3 | Programmable input A (set = Reverse Direction) |
| 4 | 4 | Relay output A (set = Reversing Contactor) |
| 5 | 5 | K1/K2 coil supply |
Manual · PDF 59 · Reverse operation contactors
Historical supplier instructions. Legend labels only; original diagram authoritative for wiring. Installation conditions and source warnings remain mandatory context.
| Source row | Label | Meaning |
|---|---|---|
| 1 | K1 | Forward run contactor |
| 2 | K2 | Reversing contactor |
Manual · PDF 60 · Inside delta unsupported options
Historical supplier instructions. Legend labels only; original diagram authoritative for wiring. Installation conditions and source warnings remain mandatory context.
| Source row | Unsupported option | Replacement behaviour |
|---|---|---|
| 1 | Adaptive control start | The starter performs a constant current start. |
| 2 | Adaptive control stop | If parameter 2J Stop Time is set >0 seconds, the starter performs a TVR soft stop. If parameter 2J is set to 0 seconds the starter performs a coast to stop. |
| 3 | Jog | The starter issues a warning with the error message Unsupported option. |
| 4 | DC brake | The starter performs a coast to stop. |
| 5 | Soft brake | The starter performs a coast to stop. |
| 6 | PowerThrough | The starter trips with the error message Lx-Tx Shorted. |
Manual · PDF 62 · Parameter summary as printed
Summary defaults as printed, not commissioned settings. Blank means blank in source. Smart-card parameters visible only when card fitted. Detailed entries may differ; retain discrepancy flags. Unspecified units are not inferred.
| Source row | Parameter ID | Parameter name | Default setting |
|---|---|---|---|
| 1 | 1A | Command Source | Digital Input |
| 2 | 1B | Motor Full Load Current | Model dependent |
| 3 | 1C | Motor kW | 0 kW |
| 4 | 1D | Locked Rotor Time | 00:10 (mm:ss) |
| 5 | 1E | Locked Rotor Current | 600% |
| 6 | 1F | Motor Service Factor | 105% |
| 7 | 1G | Reserved | ⟦blank source cell⟧ |
| 8 | 2A | Start Mode | Constant Current |
| 9 | 2B | Start Ramp Time | 00:10 (mm:ss) |
| 10 | 2C | Initial Current | 200% |
| 11 | 2D | Current Limit | 350% |
| 12 | 2E | Adaptive Start Profile | Constant Acceleration |
| 13 | 2F | Kickstart Time | 000 ms |
| 14 | 2G | Kickstart Level | 500% |
| 15 | 2H | Jog Torque | 50% |
| 16 | 2I | Stop Mode | TVR Soft Stop |
| 17 | 2J | Stop Time | 00:00 (mm:ss) |
| 18 | 2K | Adaptive Stop Profile | Constant Deceleration |
| 19 | 2L | Adaptive Control Gain | 75% |
| 20 | 2M | Multi Pump | Single Pump |
| 21 | 2N | Start Delay | 00:00 (mm:ss) |
| 22 | 2O | DC Brake Torque | 20% |
| 23 | 2P | DC Brake Time | 00:01 (mm:ss) |
| 24 | 2Q | Brake Current Limit | 250% |
| 25 | 2R | Soft Brake Delay | 400 ms |
| 26 | 3A | Motor Full Load Current-2 | Model dependent |
| 27 | 3B | Motor kW-2 | 0 kW |
| 28 | 3C | Start Mode-2 | Constant Current |
| 29 | 3D | Start Ramp Time-2 | 00:10 (mm:ss) |
| 30 | 3E | Initial Current-2 | 200% |
| 31 | 3F | Current Limit-2 | 350% |
| 32 | 3G | Adaptive Start Profile-2 | Constant Acceleration |
| 33 | 3H | Kickstart Time-2 | 000 ms |
| 34 | 3I | Kickstart Level-2 | 500% |
| 35 | 3J | Jog Torque-2 | 50% |
| 36 | 3K | Stop Mode-2 | TVR Soft Stop |
| 37 | 3L | Stop Time-2 | 00:00 (mm:ss) |
| 38 | 3M | Adaptive Stop Profile-2 | Constant Deceleration |
| 39 | 3N | Adaptive Control Gain-2 | 75% |
Manual · PDF 63 · Parameter summary as printed
Summary defaults as printed, not commissioned settings. Blank means blank in source. Smart-card parameters visible only when card fitted. Detailed entries may differ; retain discrepancy flags. Unspecified units are not inferred.
| Source row | Parameter ID | Parameter name | Default setting |
|---|---|---|---|
| 1 | 3O | Multi Pump-2 | Single Pump |
| 2 | 3P | Start Delay-2 | 00:00 (mm:ss) |
| 3 | 3Q | DC Brake Torque-2 | 20% |
| 4 | 3R | DC Brake Time-2 | 00:01 (mm:ss) |
| 5 | 3S | Brake Current Limit-2 | 250% |
| 6 | 3T | Soft Brake Delay-2 | 400 ms |
| 7 | 4A | Auto-Start/Stop Mode | Disable |
| 8 | 4B | Run Time | 00:00 (hh:mm) |
| 9 | 4C | Stopped Time | 00:00 (hh:mm) |
| 10 | 4D | Sunday Mode | Start/Stop Disable |
| 11 | 4E | Sunday Start Time | 00:00 (hh:mm) |
| 12 | 4F | Sunday Stop Time | 00:00 (hh:mm) |
| 13 | 4G | Monday Mode | Start/Stop Disable |
| 14 | 4H | Monday Start Time | 00:00 (hh:mm) |
| 15 | 4I | Monday Stop Time | 00:00 (hh:mm) |
| 16 | 4J | Tuesday Mode | Start/Stop Disable |
| 17 | 4K | Tuesday Start Time | 00:00 (hh:mm) |
| 18 | 4L | Tuesday Stop Time | 00:00 (hh:mm) |
| 19 | 4M | Wednesday Mode | Start/Stop Disable |
| 20 | 4N | Wednesday Start Time | 00:00 (hh:mm) |
| 21 | 4O | Wednesday Stop Time | 00:00 (hh:mm) |
| 22 | 4P | Thursday Mode | Start/Stop Disable |
| 23 | 4Q | Thursday Start Time | 00:00 (hh:mm) |
| 24 | 4R | Thursday Stop Time | 00:00 (hh:mm) |
| 25 | 4S | Friday Mode | Start/Stop Disable |
| 26 | 4T | Friday Start Time | 00:00 (hh:mm) |
| 27 | 4U | Friday Stop Time | 00:00 (hh:mm) |
| 28 | 4V | Saturday Mode | Start/Stop Disable |
| 29 | 4W | Saturday Start Time | 00:00 (hh:mm) |
| 30 | 4X | Saturday Stop Time | 00:00 (hh:mm) |
| 31 | 5A | Current Imbalance | 30% |
| 32 | 5B | Current Imbalance Delay | 00:03 (mm:ss) |
| 33 | 5C | Undercurrent | 20% |
| 34 | 5D | Undercurrent Delay | 00:05 (mm:ss) |
| 35 | 5E | Overcurrent | 400% |
| 36 | 5F | Overcurrent Delay | 00:00 (mm:ss) |
| 37 | 5G | Undervoltage | 350 V |
| 38 | 5H | Undervoltage Delay | 00:01 (mm:ss) |
| 39 | 5I | Overvoltage | 500 V |
| 40 | 5J | Overvoltage Delay | 00:01 (mm:ss) |
| 41 | 5K | Underpower | 10% |
| 42 | 5L | Underpower Delay | 00:05 (mm:ss) |
Manual · PDF 64 · Parameter summary as printed
Summary defaults as printed, not commissioned settings. Blank means blank in source. Smart-card parameters visible only when card fitted. Detailed entries may differ; retain discrepancy flags. Unspecified units are not inferred.
| Source row | Parameter ID | Parameter name | Default setting |
|---|---|---|---|
| 1 | 5M | Overpower | 150% |
| 2 | 5N | Overpower Delay | 00:05 (mm:ss) |
| 3 | 5O | Excess Start Time | 00:20 (mm:ss) |
| 4 | 5P | Restart Delay | 00:10 (mm:ss) |
| 5 | 5Q | Starts per Hour | 0 |
| 6 | 5R | Phase Sequence | Any Sequence |
| 7 | 6A | Auto-Reset Count | 0 |
| 8 | 6B | Auto-Reset Delay | 00:05 (mm:ss) |
| 9 | 6C | Current Imbalance | Soft Trip and Log |
| 10 | 6D | Undercurrent | Soft Trip and Log |
| 11 | 6E | Overcurrent | Soft Trip and Log |
| 12 | 6F | Undervoltage | Soft Trip and Log |
| 13 | 6G | Overvoltage | Soft Trip and Log |
| 14 | 6H | Underpower | Log Only |
| 15 | 6I | Overpower | Log Only |
| 16 | 6J | Excess Start Time | Soft Trip and Log |
| 17 | 6K | Input A Trip | Soft Trip and Log |
| 18 | 6L | Input B Trip | Soft Trip and Log |
| 19 | 6M | Network Communications | Soft Trip and Log |
| 20 | 6N | Remote Keypad Fault | Soft Trip and Log |
| 21 | 6O | Frequency | Soft Trip and Log |
| 22 | 6P | Phase Sequence | Soft Trip and Log |
| 23 | 6Q | Motor Overtemperature | Soft Trip and Log |
| 24 | 6R | Motor Thermistor Circuit | Soft Trip and Log |
| 25 | 6S | Shorted SCR Action | 3-Phase Control Only |
| 26 | 6T | Battery/Clock | Soft Trip and Log |
| 27 | 7A | Input A Function | Input Trip (N/O) |
| 28 | 7B | Input A Trip | Operating Only |
| 29 | 7C | Input A Trip Delay | 00:00 (mm:ss) |
| 30 | 7D | Input A Initial Delay | 00:00 (mm:ss) |
| 31 | 7E | Input B Function | Input Trip (N/O) |
| 32 | 7F | Input B Trip | Operating Only |
| 33 | 7G | Input B Trip Delay | 00:00 (mm:ss) |
| 34 | 7H | Input B Initial Delay | 00:00 (mm:ss) |
| 35 | 7I | Reset/Enable Logic | Normally Closed (N/C) |
| 36 | 7J | Input A Name | Input A Trip |
| 37 | 7K | Input B Name | Input B Trip |
| 38 | 8A | Relay A Function | Run |
| 39 | 8B | Relay A On Delay | 00:00 (mm:ss) |
| 40 | 8C | Relay A Off Delay | 00:00 (mm:ss) |
| 41 | 8D | Relay B Function | Run |
Manual · PDF 65 · Parameter summary as printed
Summary defaults as printed, not commissioned settings. Blank means blank in source. Smart-card parameters visible only when card fitted. Detailed entries may differ; retain discrepancy flags. Unspecified units are not inferred.
| Source row | Parameter ID | Parameter name | Default setting |
|---|---|---|---|
| 1 | 8E | Relay B On Delay | 00:00 (mm:ss) |
| 2 | 8F | Relay B Off Delay | 00:00 (mm:ss) |
| 3 | 8G | Low Current Flag | 50% |
| 4 | 8H | High Current Flag | 100% |
| 5 | 8I | Motor Temperature Flag | 80% |
| 6 | 8J | Main Contactor Time | 400 ms |
| 7 | 9A | Analog Output A | Current (% FLC) |
| 8 | 9B | Analog A Scale | 4-20 mA |
| 9 | 9C | Analog A Maximum Adjustment | 100% |
| 10 | 9D | Analog A Minimum Adjustment | 000% |
| 11 | 10A | Language | English |
| 12 | 10B | Temperature Scale | Celsius |
| 13 | 10C | Graph Timebase | 30 seconds |
| 14 | 10D | Graph Maximum Adjustment | 400% |
| 15 | 10E | Graph Minimum Adjustment | 0% |
| 16 | 10F | Current Calibration | 100% |
| 17 | 10G | Adjustment Lock | Read & Write |
| 18 | 10H | User Parameter 1 | Current |
| 19 | 10I | User Parameter 2 | Motor Voltage |
| 20 | 10J | User Parameter 3 | Mains Frequency |
| 21 | 10K | User Parameter 4 | Motor pf |
| 22 | 10L | User Parameter 5 | Motor Power |
| 23 | 10M | User Parameter 6 | Motor Temperature (%) |
| 24 | 11A | Reverse Torque | 20% |
| 25 | 11B | Reverse Time | 00:10 (mm:ss) |
| 26 | 11C | Forward Current Limit | 100% |
| 27 | 11D | Forward Time | 00:10 (mm:ss) |
| 28 | 11E | Pump Stop Mode | Coast To Stop |
| 29 | 11F | Pump Stop Time | 00:10 (mm:ss) |
| 30 | 11G | Pump Clean Cycles | 1 |
| 31 | 12A | Modbus Address | 1 |
| 32 | 12B | Modbus Baud Rate | 9600 |
| 33 | 12C | Modbus Parity | None |
| 34 | 12D | Modbus Timeout | Off |
| 35 | 12E | Devicenet Address | 0 |
| 36 | 12F | Devicenet Baud Rate | 125kB |
| 37 | 12G | Profibus Address | 1 |
| 38 | 12H | Gateway Address | 192 |
| 39 | 12I | Gateway Address 2 | 168 |
Manual · PDF 66 · Parameter summary as printed
Summary defaults as printed, not commissioned settings. Blank means blank in source. Smart-card parameters visible only when card fitted. Detailed entries may differ; retain discrepancy flags. Unspecified units are not inferred.
| Source row | Parameter ID | Parameter name | Default setting |
|---|---|---|---|
| 1 | 12J | Gateway Address 3 | 0 |
| 2 | 12K | Gateway Address 4 | 100 |
| 3 | 12L | IP Address | 192 |
| 4 | 12M | IP Address 2 | 168 |
| 5 | 12N | IP Address 3 | 0 |
| 6 | 12O | IP Address 4 | 2 |
| 7 | 12P | Subnet Mask | 255 |
| 8 | 12Q | Subnet Mask 2 | 255 |
| 9 | 12R | Subnet Mask 3 | 255 |
| 10 | 12S | Subnet Mask 4 | 0 |
| 11 | 12T | DHCP | Disable |
| 12 | 12U | Location ID | 0 |
| 13 | 20A | Tracking Gain | 50% |
| 14 | 20B | Pedestal Detect | 80% |
| 15 | 20C | Bypass Contactor Delay | 100 ms |
| 16 | 20D | Model Rating | Model dependent |
| 17 | 20E | Screen Timeout | 1 minute |
| 18 | 20F | Motor Connection | Auto-detect |
| 19 | 20G | External Bypass | Disable |
| 20 | 20H | Shunt Trip Mode | Disable |
| 21 | 30A | Pressure Sensor Type | None |
| 22 | 30B | Pressure Units | kPa |
| 23 | 30C | Pressure at 4 mA | 0 |
| 24 | 30D | Pressure at 20 mA | 0 |
| 25 | 30E | Flow Sensor Type | None |
| 26 | 30F | Flow Units | litres/second |
| 27 | 30G | Flow at 4 mA | 0 |
| 28 | 30H | Flow at 20 mA | 0 |
| 29 | 30I | Units per Minute at Max Flow | 0 |
| 30 | 30J | Pulses per Minute at Max Flow | 0 |
| 31 | 30K | Units per Pulse | 0 |
| 32 | 30L | Depth Sensor Type | None |
| 33 | 30M | Depth Units | metres |
| 34 | 30N | Depth at 4 mA | 0 |
| 35 | 30O | Depth at 20 mA | 0 |
| 36 | 31A | High Flow Trip Level | 10 |
| 37 | 31B | Low Flow Trip Level | 5 |
| 38 | 31C | Flow Start Delay | 00:00:500 (mm:ss:ms) |
| 39 | 31D | Flow Response Delay | 00:00:500 (mm:ss:ms) |
Manual · PDF 67 · Parameter summary as printed
Summary defaults as printed, not commissioned settings. Blank means blank in source. Smart-card parameters visible only when card fitted. Detailed entries may differ; retain discrepancy flags. Unspecified units are not inferred.
| Source row | Parameter ID | Parameter name | Default setting |
|---|---|---|---|
| 1 | 32A | High Pressure Trip Level | 10 |
| 2 | 32B | High Pressure Start Delay | 00:00:500 (mm:ss:ms) |
| 3 | 32C | High Pressure Response Delay | 00:00:500 (mm:ss:ms) |
| 4 | 32D | Low Pressure Trip Level | 5 |
| 5 | 32E | Low Pressure Start Delay | 00:00:500 (mm:ss:ms) |
| 6 | 32F | Low Pressure Response Delay | 00:00:500 (mm:ss:ms) |
| 7 | 33A | Pressure Control Mode | Off |
| 8 | 33B | Start Pressure Level | 5 |
| 9 | 33C | Start Response Delay | 00:00:500 (mm:ss:ms) |
| 10 | 33D | Stop Pressure Level | 10 |
| 11 | 33E | Stop Response Delay | 00:00:500 (mm:ss:ms) |
| 12 | 34A | Depth Trip Level | 5 |
| 13 | 34B | Depth Reset Level | 10 |
| 14 | 34C | Depth Start Delay | 00:00:500 (mm:ss:ms) |
| 15 | 34D | Depth Response Delay | 00:00:500 (mm:ss:ms) |
| 16 | 35A | Temperature Sensor Type | None |
| 17 | 35B | Temperature Trip Level | 40 |
| 18 | 36A | Pressure Sensor | Soft Trip and Log |
| 19 | 36B | Flow Sensor | Soft Trip and Log |
| 20 | 36C | Depth Sensor | Soft Trip and Log |
| 21 | 36D | High Pressure | Soft Trip and Log |
| 22 | 36E | Low Pressure | Soft Trip and Log |
| 23 | 36F | High Flow | Soft Trip and Log |
| 24 | 36G | Low Flow | Soft Trip and Log |
| 25 | 36H | Flow Switch | Soft Trip and Log |
| 26 | 36I | Well Depth | Soft Trip and Log |
| 27 | 36J | RTD/PT100 B | Soft Trip and Log |
| 28 | 40A | Ground Fault Level | 0 A |
| 29 | 40B | Ground Fault Delay | 00:01 (mm:ss) |
| 30 | 40D | Ground Fault Trip Active | Operating only |
| 31 | 40C | Ground Fault Action | Soft Trip and Log |
| 32 | 40E | Ground Fault CT Ratio | 1000:1 |
| 33 | 41A | 4mA Calibration | 100% |
| 34 | 41B | 20mA Calibration | 100% |
Manual · PDF 68 · 1B – Motor Full Load Current
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range |
|---|---|
| 1 | Model dependent |
Manual · PDF 68 · 1C – Motor kW
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 9999 kW | 0 |
Manual · PDF 68 · 1D – Locked Rotor Time
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:01 - 2:00 (minutes:seconds) | 10 seconds |
Manual · PDF 68 · 1E – Locked Rotor Current
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 400% - 1200% FLC | 600% |
Manual · PDF 68 · 1A Command Source option meanings
Options are alternatives, not combined modes. Default marker retained exactly. Full source restrictions remain authoritative.
| Source row | Option | Meaning |
|---|---|---|
| 1 | Digital Input (default) | The soft starter will accept start and stop commands from the digital inputs. |
| 2 | Network | The soft starter will accept start and stop commands from the communication expansion card. |
| 3 | Remote Keypad | The soft starter will accept start and stop commands from the Remote Keypad. |
| 4 | Clock | The soft starter will start and stop as scheduled in parameters 4D to 4X. |
| 5 | Smart Card | The soft starter will accept start and stop commands from the smart card. |
| 6 | Smart Card + Clock | The soft starter will accept start commands from the smart card if they are within the operating schedule set in parameters 4D to 4X. A stop command from the smart card will be accepted regardless of the schedule. |
| 7 | Timer | After a start signal is received, the soft starter will start and stop the motor according to the timers set in parameters 4B and 4C. |
Manual · PDF 69 · 1F – Motor Service Factor
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 100% - 130% | 105% |
Manual · PDF 69 · 2B – Start Ramp Time
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:01 - 3:00 (minutes:seconds) | 10 seconds |
Manual · PDF 69 · 2C – Initial Current
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 100% - 600% FLC | 200% |
Manual · PDF 69 · 2D – Current Limit
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 100% - 600% FLC | 350% |
Manual · PDF 70 · 2F – Kickstart Time
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 – 2000 milliseconds | 0000 milliseconds |
Manual · PDF 70 · 2G – Kickstart Level
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 100% - 700% FLC | 500% |
Manual · PDF 70 · 2H – Jog Torque
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 20% - 100% | 50% |
Manual · PDF 70 · 2J – Stop Time
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 4:00 (minutes:seconds) | 0 second |
Manual · PDF 70 · 2L – Adaptive Control Gain
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 1% - 200% | 75% |
Manual · PDF 71 · 2N – Start Delay
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 60:00 (minutes:seconds) | 0 second |
Manual · PDF 71 · 2O – DC Brake Torque
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 20% - 100% | 20% |
Manual · PDF 71 · 2P – DC Brake Time
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:01 - 0:30 (minutes:seconds) | 1 second |
Manual · PDF 71 · 2Q – Brake Current Limit
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 100% - 600% FLC | 250% |
Manual · PDF 71 · 2R – Soft Brake Delay
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 400 - 2000 milliseconds | 400 milliseconds |
Manual · PDF 71 · 3A – Motor Full Load Current-2
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range |
|---|---|
| 1 | Model dependent |
Manual · PDF 71 · 3B – Motor kW-2
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 9999 kW | 0 |
Manual · PDF 72 · 3D – Start Ramp Time-2
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:01 - 3:00 (minutes:seconds) | 10 seconds |
Manual · PDF 72 · 3E – Initial Current-2
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 100% - 600% FLC | 200% |
Manual · PDF 72 · 3F – Current Limit-2
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 100% - 600% FLC | 350% |
Manual · PDF 72 · 3H – Kickstart Time-2
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 – 2000 milliseconds | 0000 milliseconds |
Manual · PDF 72 · 3I – Kickstart Level-2
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 100% - 700% FLC | 500% |
Manual · PDF 72 · 3J – Jog Torque-2
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 20% - 100% | 50% |
Manual · PDF 73 · 3L – Stop Time-2
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 4:00 (minutes:seconds) | 0 second |
Manual · PDF 73 · 3N – Adaptive Control Gain-2
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 1%~200% | 75% |
Manual · PDF 73 · 3P – Start Delay-2
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 60:00 (minutes:seconds) | 0 second |
Manual · PDF 73 · 3Q – DC Brake Torque-2
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 20% - 100% | 20% |
Manual · PDF 73 · 3R – DC Brake Time-2
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:01 - 0:30 (minutes:seconds) | 1 second |
Manual · PDF 73 · 3S – Brake Current Limit-2
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 100% - 600% FLC | 250% |
Manual · PDF 73 · 3T – Soft Brake Delay-2
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 400 - 2000 milliseconds | 400 milliseconds |
Manual · PDF 74 · 4B – Run Time
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 hh:mm | 00:00 |
Manual · PDF 74 · 4C – Stopped Time
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 hh:mm | 00:00 |
Manual · PDF 74 · 4E – Sunday Start Time
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 | 00:00 |
Manual · PDF 74 · 4F – Sunday Stop Time
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 | 00:00 |
Manual · PDF 74 · 4H – Monday Start Time
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 | 00:00 |
Manual · PDF 74 · 4I – Monday Stop Time
Exact detailed parameter range/default; units as printed. Parameter descriptions, motor/application conditions and warnings are inseparable source context.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 | 00:00 |
Manual · PDF 74 · 4D Sunday Mode option meanings
Options are alternatives, not combined modes. Default marker retained exactly. Full source restrictions remain authoritative.
| Source row | Option | Meaning |
|---|---|---|
| 1 | Start/Stop Disable (default) | Disables auto-start/stop control. Any times scheduled in parameters 4E or 4F will be ignored. |
| 2 | Start Only Enable | Enables auto-start control. Any auto-stop times scheduled in parameter 4F will be ignored. |
| 3 | Stop Only Enable | Enables auto-stop control. Any auto-start times scheduled in parameter 4E will be ignored. |
| 4 | Start/Stop Enable | Enables auto-start and auto-stop control. |
Manual · PDF 75 · 4K – Tuesday Start Time
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 | 00:00 |
Manual · PDF 75 · 4L – Tuesday Stop Time
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 | 00:00 |
Manual · PDF 75 · 4N – Wednesday Start Time
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 | 00:00 |
Manual · PDF 75 · 4O – Wednesday Stop Time
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 | 00:00 |
Manual · PDF 75 · 4Q – Thursday Start Time
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 | 00:00 |
Manual · PDF 75 · 4R – Thursday Stop Time
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 | 00:00 |
Manual · PDF 75 · 4T – Friday Start Time
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 | 00:00 |
Manual · PDF 75 · 4J – Tuesday Mode
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Start/Stop Disable (default) |
| 2 | Start Only Enable |
| 3 | Stop Only Enable |
| 4 | Start/Stop Enable |
Manual · PDF 75 · 4M – Wednesday Mode
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Start/Stop Disable (default) |
| 2 | Start Only Enable |
| 3 | Stop Only Enable |
| 4 | Start/Stop Enable |
Manual · PDF 75 · 4P – Thursday Mode
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Start/Stop Disable (default) |
| 2 | Start Only Enable |
| 3 | Stop Only Enable |
| 4 | Start/Stop Enable |
Manual · PDF 75 · 4S – Friday Mode
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Start/Stop Disable (default) |
| 2 | Start Only Enable |
| 3 | Stop Only Enable |
| 4 | Start/Stop Enable |
Manual · PDF 76 · 4U – Friday Stop Time
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 | 00:00 |
Manual · PDF 76 · 4W – Saturday Start Time
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 | 00:00 |
Manual · PDF 76 · 4X – Saturday Stop Time
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 23:59 | 00:00 |
Manual · PDF 76 · 5A – Current Imbalance
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 10% - 50% | 30% |
Manual · PDF 76 · 5B – Current Imbalance Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 4:00 (minutes:seconds) | 3 seconds |
Manual · PDF 76 · 5C – Undercurrent
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0% - 100% | 20% |
Manual · PDF 76 · 5D – Undercurrent Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 4:00 (minutes:seconds) | 5 seconds |
Manual · PDF 76 · 5E – Overcurrent
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 80% - 600% | 400% |
Manual · PDF 76 · 5F – Overcurrent Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 1:00 (minutes:seconds) | 0 second |
Manual · PDF 76 · 4V – Saturday Mode
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Start/Stop Disable (default) |
| 2 | Start Only Enable |
| 3 | Stop Only Enable |
| 4 | Start/Stop Enable |
Manual · PDF 77 · 5G – Undervoltage
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 100 - 1200 V | 350 |
Manual · PDF 77 · 5H – Undervoltage Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 1:00 (minutes:seconds) | 1 second |
Manual · PDF 77 · 5I – Overvoltage
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 100 - 1500 V | 500 |
Manual · PDF 77 · 5J – Overvoltage Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 1:00 (minutes:seconds) | 1 second |
Manual · PDF 77 · 5K – Underpower
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 10% -120% | 10% |
Manual · PDF 77 · 5L – Underpower Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:01 - 1:00 (minutes:seconds) | 5 seconds |
Manual · PDF 77 · 5M – Overpower
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 80% -200% | 150% |
Manual · PDF 77 · 5N – Overpower Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:01 - 1:00 (minutes:seconds) | 5 seconds |
Manual · PDF 77 · 5O – Excess Start Time
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 4:00 (minutes:seconds) | 20 seconds |
Manual · PDF 78 · 5P – Restart Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:01 - 60:00 (minutes:seconds) | 10 seconds |
Manual · PDF 78 · 5Q – Starts per Hour
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 10 | 0 |
Manual · PDF 78 · 6A – Auto-Reset Count
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 – 5 | 0 |
Manual · PDF 78 · 6B – Auto-Reset Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:05 - 15:00 (minutes:seconds) | 5 seconds |
Manual · PDF 78 · 5R – Phase Sequence
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Any Sequence (default) |
| 2 | Positive Only |
| 3 | Negative Only |
Manual · PDF 78 · 6C – Current Imbalance
Each option mapped to its own source meaning. Option defaults and restrictions retained verbatim. Continuation on adjacent source pages explicitly identified.
| Source row | Option | Meaning |
|---|---|---|
| 1 | Soft Trip and Log (default) | The soft starter will stop the motor as selected in parameter 2I or 3K Stop Mode, then enter trip state. The trip must be reset before the starter can restart. |
| 2 | Soft Trip and Reset | The soft starter will stop the motor as selected in parameter 2I or 3K Stop Mode, then enter trip state. The trip will reset after the auto-reset delay. |
| 3 | Trip Starter | The soft starter will remove power and the motor will coast to stop. The trip must be reset before the starter can restart. |
| 4 | Trip and Reset | The soft starter will remove power and the motor will coast to stop. The trip will reset after the auto-reset delay. |
Manual · PDF 79 · 6C – Current Imbalance continuation
Each option mapped to its own source meaning. Option defaults and restrictions retained verbatim. Continuation on adjacent source pages explicitly identified.
| Source row | Option | Meaning |
|---|---|---|
| 1 | Warn and Log | The protection will be written to the event log and the display will show a warning message, but the soft starter will continue to operate. |
| 2 | Log Only | The protection will be written to the event log but the soft starter will continue to operate. |
| 3 | Trip + Shunt Relay | The soft starter will remove power and the motor will coast to stop. The shunt trip relay (33, 34) will activate and the circuit breaker will disconnect mains voltage from the soft starter. The circuit breaker must be manually reset before operation can resume. This option is only effective if parameter 20H Shunt Trip Mode is set to 'Enable'. |
Manual · PDF 79 · 6D – Undercurrent
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Soft Trip and Log (default) |
| 2 | Soft Trip and Reset |
| 3 | Trip Starter |
| 4 | Trip and Reset |
| 5 | Warn and Log |
| 6 | Log Only |
| 7 | Trip + Shunt Relay |
Manual · PDF 79 · 6E – Overcurrent
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Soft Trip and Log (default) |
| 2 | Soft Trip and Reset |
| 3 | Trip Starter |
| 4 | Trip and Reset |
| 5 | Warn and Log |
| 6 | Log Only |
| 7 | Trip + Shunt Relay |
Manual · PDF 79 · 6F – Undervoltage
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Soft Trip and Log (default) |
| 2 | Soft Trip and Reset |
| 3 | Trip Starter |
| 4 | Trip and Reset |
| 5 | Warn and Log |
| 6 | Log Only |
| 7 | Trip + Shunt Relay |
Manual · PDF 79 · 6G – Overvoltage
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Soft Trip and Log (default) |
| 2 | Soft Trip and Reset |
| 3 | Trip Starter |
| 4 | Trip and Reset |
| 5 | Warn and Log |
| 6 | Log Only |
| 7 | Trip + Shunt Relay |
Manual · PDF 79 · 6H – Underpower
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Log Only (default) |
| 2 | Trip + Shunt Relay |
| 3 | Soft Trip and Log |
| 4 | Soft Trip and Reset |
| 5 | Trip Starter |
| 6 | Trip and Reset |
| 7 | Warn and Log |
Manual · PDF 80 · 6I – Overpower
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Log Only (default) |
| 2 | Trip + Shunt Relay |
| 3 | Soft Trip and Log |
| 4 | Soft Trip and Reset |
| 5 | Trip Starter |
| 6 | Trip and Reset |
| 7 | Warn and Log |
Manual · PDF 80 · 6J – Excess Start Time
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Soft Trip and Log (default) |
| 2 | Soft Trip and Reset |
| 3 | Trip Starter |
| 4 | Trip and Reset |
| 5 | Warn and Log |
| 6 | Log Only |
| 7 | Trip + Shunt Relay |
Manual · PDF 80 · 6K – Input A Trip
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Soft Trip and Log (default) |
| 2 | Soft Trip and Reset |
| 3 | Trip Starter |
| 4 | Trip and Reset |
| 5 | Warn and Log |
| 6 | Log Only |
| 7 | Trip + Shunt Relay |
Manual · PDF 80 · 6L – Input B Trip
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Soft Trip and Log (default) |
| 2 | Soft Trip and Reset |
| 3 | Trip Starter |
| 4 | Trip and Reset |
| 5 | Warn and Log |
| 6 | Log Only |
| 7 | Trip + Shunt Relay |
Manual · PDF 80 · 6M – Network Communications
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Soft Trip and Log (default) |
| 2 | Soft Trip and Reset |
| 3 | Trip Starter |
| 4 | Trip and Reset |
| 5 | Warn and Log |
| 6 | Log Only |
| 7 | Stop |
| 8 | Trip + Shunt Relay |
Manual · PDF 80 · 6N – Remote Keypad Fault
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Soft Trip and Log (default) |
| 2 | Soft Trip and Reset |
| 3 | Trip Starter |
| 4 | Trip and Reset |
| 5 | Warn and Log |
| 6 | Log Only |
| 7 | Trip + Shunt Relay |
Manual · PDF 81 · 6O – Frequency
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Soft Trip and Log (default) |
| 2 | Soft Trip and Reset |
| 3 | Trip Starter |
| 4 | Trip and Reset |
| 5 | Warn and Log |
| 6 | Log Only |
| 7 | Trip + Shunt Relay |
Manual · PDF 81 · 6P – Phase Sequence
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Soft Trip and Log (default) |
| 2 | Soft Trip and Reset |
| 3 | Trip Starter |
| 4 | Trip and Reset |
| 5 | Warn and Log |
| 6 | Log Only |
| 7 | Trip + Shunt Relay |
Manual · PDF 81 · 6Q – Motor Overtemperature
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Soft Trip and Log (default) |
| 2 | Soft Trip and Reset |
| 3 | Trip Starter |
| 4 | Trip and Reset |
| 5 | Warn and Log |
| 6 | Log Only |
| 7 | Trip + Shunt Relay |
Manual · PDF 81 · 6R – Motor Thermistor Circuit
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Soft Trip and Log (default) |
| 2 | Soft Trip and Reset |
| 3 | Trip Starter |
| 4 | Trip and Reset |
| 5 | Warn and Log |
| 6 | Log Only |
| 7 | Trip + Shunt Relay |
Manual · PDF 81 · 6S – Shorted SCR Action
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | 3-Phase Control Only (default) |
| 2 | PowerThrough |
| 3 | Trip + Shunt Relay |
Manual · PDF 81 · 6T – Battery/Clock
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Soft Trip and Log (default) |
| 2 | Soft Trip and Reset |
| 3 | Trip Starter |
| 4 | Trip and Reset |
| 5 | Warn and Log |
| 6 | Log Only |
| 7 | Trip + Shunt Relay |
Manual · PDF 82 · 7C – Input A Trip Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 4:00 (minutes:seconds) | 0 second |
Manual · PDF 82 · 7D – Input A Initial Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 30:00 (minutes:seconds) | 0 second |
Manual · PDF 82 · 7A – Input A Function
Each option mapped to its own source meaning. Option defaults and restrictions retained verbatim. Continuation on adjacent source pages explicitly identified.
| Source row | Option | Meaning |
|---|---|---|
| 1 | Command Override: Network | Overrides the setting of 1A and sets the command source to the communications network. |
| 2 | Command Override: Digital | Overrides the setting of 1A and sets the command source to the digital inputs. |
| 3 | Command Override: Keypad | Overrides the setting of 1A and sets the command source to the remote keypad. |
| 4 | Input Trip (N/O) (default) | A closed circuit across 13, 14 trips the soft starter. |
| 5 | Input Trip (N/C) | An open circuit across 13, 14 trips the soft starter. |
| 6 | Emergency Mode | A closed circuit across 13, 14 activates emergency mode. When the soft starter receives a start command, it will continue to run until a stop command is received, ignoring all trips and warnings. |
| 7 | Jog Forward | Activates jog operation in a forward direction. |
| 8 | Jog Reverse | Activates jog operation in reverse direction. |
| 9 | Zero Speed Sensor | An open circuit across 13, 14 indicates to the soft starter that the motor has reached a standstill. The soft starter requires a normally open zero speed sensor. |
| 10 | Motor Set Select | A closed circuit across 13, 14 instructs the starter to use the secondary motor configuration for the next start/stop cycle. |
| 11 | Reverse Direction | A closed circuit across 13, 14 instructs the starter to reverse the phase sequence for the next start. |
| 12 | Pump Clean | Activates the pump clean function. |
Manual · PDF 82 · 7B – Input A Trip
Each option mapped to its own source meaning. Option defaults and restrictions retained verbatim. Continuation on adjacent source pages explicitly identified.
| Source row | Option | Meaning |
|---|---|---|
| 1 | Always Active | A trip can occur at any time when the soft starter is receiving power. |
| 2 | Operating Only (default) | A trip can occur while the soft starter is running, stopping or starting. |
| 3 | Run Only | A trip can only occur while the soft starter is running. |
Manual · PDF 83 · 7G – Input B Trip Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 4:00 (minutes:seconds) | 0 second |
Manual · PDF 83 · 7H – Input B Initial Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 - 30:00 (minutes:seconds) | 0 second |
Manual · PDF 83 · 7E – Input B Function
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Input Trip (N/O) (default) |
| 2 | Input Trip (N/C) |
| 3 | Emergency Mode |
| 4 | Jog Forward |
| 5 | Jog Reverse |
| 6 | Zero Speed Sensor |
| 7 | Motor Set Select |
| 8 | Reverse Direction |
| 9 | Pump Clean |
Manual · PDF 83 · 7F – Input B Trip
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Always Active |
| 2 | Operating Only (default) |
| 3 | Run Only |
Manual · PDF 83 · 7I – Reset/Enable Logic
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Normally Closed (default) |
| 2 | Normally Open |
Manual · PDF 83 · 7J – Input A Name
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Input A Trip (default) |
| 2 | Low Pressure |
| 3 | High Pressure |
| 4 | Pump Fault |
| 5 | Low Level |
| 6 | High Level |
| 7 | No Flow |
| 8 | Starter Disable |
| 9 | Controller |
| 10 | PLC |
| 11 | Vibration Alarm |
| 12 | Field Trip |
| 13 | Interlock Trip |
| 14 | Motor Temperature |
| 15 | Motor Protection |
| 16 | Feeder Protection |
| 17 | Custom Message |
Manual · PDF 84 · 7K – Input B Name
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Input B Trip (default) |
| 2 | Low Pressure |
| 3 | High Pressure |
| 4 | Pump Fault |
| 5 | Low Level |
| 6 | High Level |
| 7 | No Flow |
| 8 | Starter Disable |
| 9 | Controller |
| 10 | PLC |
| 11 | Vibration Alarm |
| 12 | Field Trip |
| 13 | Interlock Trip |
| 14 | Motor Temperature |
| 15 | Motor Protection |
| 16 | Feeder Protection |
| 17 | Custom Message |
Manual · PDF 84 · 8A – Relay A Function
Each option mapped to its own source meaning. Option defaults and restrictions retained verbatim. Continuation on adjacent source pages explicitly identified.
| Source row | Option | Meaning |
|---|---|---|
| 1 | Off | Relay A is not used. |
| 2 | Ready | The relay is closed when the starter is in Ready state. |
| 3 | Run (default) | The Run output closes when the soft start is complete (when the starting current falls below 120% of the programmed motor full load current) and remains closed until the beginning of a stop (either soft stop or coast to stop). |
| 4 | Warning | The relay closes when the starter issues a warning (see 6 Protection Action on page 76). |
| 5 | Trip | The relay closes when the starter trips (see 6 Protection Action on page 76). |
| 6 | Low Current Flag | The relay closes when the low current flag activates while the motor is running (see parameter 8G Low Current Flag). |
| 7 | High Current Flag | The relay closes when the high current flag activates while the motor is running (see parameter 8H High Current Flag). |
| 8 | Motor Temperature Flag | The relay closes when the motor temperature flag activates (see parameter 8I Motor Temperature Flag). |
| 9 | Soft Brake Relay | The relay closes when the soft starter receives a stop signal, and remains closed until the end of soft brake. |
| 10 | Reversing Contactor | The relay will control an external contactor, for reverse operation. See Reverse direction operation on page 56 for details. |
| 11 | Trip Failsafe | The relay closes when control power is applied. The relay opens if the soft starter trips or if control power is lost. |
| 12 | Operating Only | The relay is closed while the soft starter is running, stopping or starting. |
Manual · PDF 85 · 8B – Relay A On Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 5:00 (minutes:seconds) | 0 second |
Manual · PDF 85 · 8C – Relay A Off Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 5:00 (minutes:seconds) | 0 second |
Manual · PDF 85 · 8E – Relay B On Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 5:00 (minutes:seconds) | 0 second |
Manual · PDF 85 · 8F – Relay B Off Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 5:00 (minutes:seconds) | 0 second |
Manual · PDF 85 · 8G – Low Current Flag
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 1% - 100% FLC | 50% |
Manual · PDF 85 · 8H – High Current Flag
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 50% - 600% FLC | 100% |
Manual · PDF 85 · 8I – Motor Temperature Flag
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0% - 160% | 80% |
Manual · PDF 85 · 8D – Relay B Function
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Off |
| 2 | Ready |
| 3 | Run (default) |
| 4 | Warning |
| 5 | Trip |
| 6 | Low Current Flag |
| 7 | High Current Flag |
| 8 | Motor Temperature Flag |
| 9 | Soft Brake Relay |
| 10 | Reversing Contactor |
| 11 | Trip Failsafe |
| 12 | Operating Only |
Manual · PDF 86 · 8J – Main Contactor Time
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 100 – 2000 milliseconds | 400 milliseconds |
Manual · PDF 86 · 9C – Analog A Maximum Adjustment
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0% - 600% | 100% |
Manual · PDF 86 · 9D – Analog A Minimum Adjustment
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0% - 600% | 0% |
Manual · PDF 86 · 9A – Analog Output A
Each option mapped to its own source meaning. Option defaults and restrictions retained verbatim. Continuation on adjacent source pages explicitly identified.
| Source row | Option | Meaning |
|---|---|---|
| 1 | Current (% FLC) (default) | Current as a percentage of motor full load current. |
| 2 | Motor Temperature (%) | The motor's temperature, calculated by the thermal model. |
| 3 | Motor pf | Motor power factor, measured by the soft starter. |
| 4 | Motor Power (%kW) | Motor power, as a percentage of the programmed power. |
| 5 | Heatsink Temperature (%) | The soft starter's temperature, as a percentage of the heatsink's maximum allowed operating temperature. |
Manual · PDF 86 · 9B – Analog A Scale
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | 0-20 mA |
| 2 | 4-20 mA (default) |
Manual · PDF 87 · 10D – Graph Maximum Adjustment
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0% – 600% | 400% |
Manual · PDF 87 · 10E – Graph Minimum Adjustment
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0% – 600% | 0% |
Manual · PDF 87 · 10F – Current Calibration
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 85% - 115% | 100% |
Manual · PDF 87 · 10A – Language
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | English (default) |
| 2 | Chinese |
| 3 | Español |
| 4 | Deutsch |
| 5 | Português |
| 6 | Français |
| 7 | Italiano |
| 8 | Russian |
Manual · PDF 87 · 10B – Temperature Scale
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Celsius (default) |
| 2 | Fahrenheit |
Manual · PDF 87 · 10C – Graph Timebase
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | 30 seconds (default) |
| 2 | 1 minute |
| 3 | 30 minutes |
| 4 | 1 hour |
Manual · PDF 87 · 10G – Adjustment Lock
Each option mapped to its own source meaning. Option defaults and restrictions retained verbatim. Continuation on adjacent source pages explicitly identified.
| Source row | Option | Meaning |
|---|---|---|
| 1 | Read & Write (default) | Allows users to alter parameter values in the main menu. |
| 2 | Read Only | Prevents users altering parameter values in the main menu. Parameter values can still be viewed. |
Manual · PDF 88 · 10H – User Parameter 1
Each option mapped to its own source meaning. Option defaults and restrictions retained verbatim. Continuation on adjacent source pages explicitly identified.
| Source row | Option | Meaning |
|---|---|---|
| 1 | Blank | Displays no data in the selected area, allowing long messages to be shown without overlapping. |
| 2 | Current (default) | Average rms current across all three phases |
| 3 | Motor Voltage | Average rms voltage across all three phases. |
| 4 | P1 Voltage | Phase 1 voltage. |
| 5 | P2 Voltage | Phase 2 voltage. |
| 6 | P3 Voltage | Phase 3 voltage. |
| 7 | Mains Frequency | The average frequency measured on three phases. |
| 8 | Motor pf | The motor's power factor, measured by the soft starter. |
| 9 | Motor Power | The motor's running power in kilowatts. |
| 10 | Motor Temperature (%) | The motor's temperature, calculated by the thermal model. |
| 11 | Hours Run | The number of hours the motor has run via the soft starter. |
| 12 | Number of Starts | The number of starts the soft starter has completed since the start counter was last reset. |
| 13 | Pump Pressure | The pressure at the pump, as configured in parameters 30B~30D. This information is only available if the smart card is installed. |
| 14 | Pump Flow | The flow at the pump, as configured in parameters 30F~30K. This information is only available if the smart card is installed. |
| 15 | Well Depth | The depth of the well, as configured in parameters 30M~30O. This information is only available if the smart card is installed. |
| 16 | Pump Temperature | The pump temperature, as measured by the PT100. This information is only available if the smart card is installed. |
| 17 | Analog Output Value | The value of the analog output (see parameters 9A~9D). |
| 18 | Heatsink Temperature | The soft starter's temperature, measured at the heatsink. |
| 19 | Bypass Model (%) | The percentage of thermal capacity remaining in the bypass contactor. |
| 20 | SCR Temperature | The temperature of the SCRs, calculated by the thermal model. |
| 21 | Rating Capacity (%) | The thermal capacity available in the soft starter for its next start. |
Manual · PDF 88 · 10I – User Parameter 2
Options reference and default are separate source columns. Referenced options remain in source, not inferred.
| Source row | Options reference | Default |
|---|---|---|
| 1 | See parameter 10H User Parameter 1 for details. | Motor Voltage |
Manual · PDF 89 · 11A – Reverse Torque
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 20% - 100% | 20% |
Manual · PDF 89 · 11B – Reverse Time
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 1:00 (minutes:seconds) | 10 seconds |
Manual · PDF 89 · 11C – Forward Current Limit
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 100% - 600% FLC | 100% |
Manual · PDF 89 · 10J – User Parameter 3
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Blank |
| 2 | Current (default) |
| 3 | Motor Voltage |
| 4 | P1 Voltage |
| 5 | P2 Voltage |
| 6 | P3 Voltage |
| 7 | Mains Frequency (default) |
| 8 | Motor pf |
| 9 | Motor Power |
| 10 | Motor Temperature (%) |
| 11 | Hours Run |
| 12 | Number of Starts |
| 13 | Pump Pressure |
| 14 | Pump Flow |
| 15 | Well Depth |
| 16 | Pump Temperature |
| 17 | Analog Output Value |
| 18 | Heatsink Temperature |
| 19 | Bypass Model (%) |
| 20 | SCR Temperature |
| 21 | Rating Capacity (%) |
| 22 | Ground Fault |
Manual · PDF 89 · 10K – User Parameter 4
Options reference and default are separate source columns. Referenced options remain in source, not inferred.
| Source row | Options reference | Default |
|---|---|---|
| 1 | See parameter 10J User Parameter 3 for details. | Motor pf |
Manual · PDF 89 · 10L – User Parameter 5
Options reference and default are separate source columns. Referenced options remain in source, not inferred.
| Source row | Options reference | Default |
|---|---|---|
| 1 | See parameter 10J User Parameter 3 for details. | Motor Power |
Manual · PDF 89 · 10M – User Parameter 6
Options reference and default are separate source columns. Referenced options remain in source, not inferred.
| Source row | Options reference | Default |
|---|---|---|
| 1 | See parameter 10J User Parameter 3 for details. | Motor Temperature (%) |
Manual · PDF 90 · 11D – Forward Time
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 1:00 (minutes:seconds) | 10 seconds |
Manual · PDF 90 · 11F – Pump Stop Time
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0:00 - 1:00 (minutes:seconds) | 10 seconds |
Manual · PDF 90 · 11G – Pump Clean Cycles
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 1 – 5 | 1 |
Manual · PDF 90 · 12A – Modbus Address
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 1 - 254 | 1 |
Manual · PDF 90 · 12E – Devicenet Address
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 63 | 0 |
Manual · PDF 90 · 11E – Pump Stop Mode
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Coast To Stop (default) |
| 2 | TVR Soft Stop |
Manual · PDF 90 · 12B – Modbus Baud Rate
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | 4800 |
| 2 | 9600 (default) |
| 3 | 19200 |
| 4 | 38400 |
Manual · PDF 90 · 12C – Modbus Parity
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | None (default) |
| 2 | Odd |
| 3 | Even |
| 4 | 10-bit |
Manual · PDF 90 · 12D – Modbus Timeout
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Off (default) |
| 2 | 10 seconds |
| 3 | 60 seconds |
| 4 | 100 seconds |
Manual · PDF 91 · 12G – Profibus Address
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 1 - 125 | 1 |
Manual · PDF 91 · 12H – Gateway Address
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 255 | 192 |
Manual · PDF 91 · 12I – Gateway Address 2
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 255 | 168 |
Manual · PDF 91 · 12J – Gateway Address 3
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 255 | 0 |
Manual · PDF 91 · 12K – Gateway Address 4
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 255 | 100 |
Manual · PDF 91 · 12L – IP Address
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 255 | 192 |
Manual · PDF 91 · 12M – IP Address 2
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 255 | 168 |
Manual · PDF 91 · 12N – IP Address 3
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 255 | 0 |
Manual · PDF 91 · 12O – IP Address 4
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 255 | 2 |
Manual · PDF 91 · 12F – Devicenet Baud Rate
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | 125 kB (default) |
| 2 | 250 kB |
| 3 | 500 kB |
Manual · PDF 92 · 12P – Subnet Mask
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 255 | 255 |
Manual · PDF 92 · 12Q – Subnet Mask 2
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 255 | 255 |
Manual · PDF 92 · 12R – Subnet Mask 3
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 255 | 255 |
Manual · PDF 92 · 12S – Subnet Mask 4
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 255 | 0 |
Manual · PDF 92 · 12U – Location ID
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 - 65535 | 0 |
Manual · PDF 92 · 20A – Tracking Gain
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 1% - 200% | 50% |
Manual · PDF 92 · 12T – DHCP
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Disable (default) |
| 2 | Enable |
Manual · PDF 93 · 20B – Pedestal Detect
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0% - 200% | 80% |
Manual · PDF 93 · 20C – Bypass Contactor Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 50 – 200 milliseconds | 100 milliseconds |
Manual · PDF 93 · 20D – Model Rating
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range |
|---|---|
| 1 | Model dependent |
Manual · PDF 93 · 20E – Screen Timeout
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | 1 minute (default) |
| 2 | 2 minutes |
| 3 | 3 minutes |
| 4 | 4 minutes |
| 5 | 5 minutes |
Manual · PDF 93 · 20F – Motor Connection
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Auto-detect (default) |
| 2 | In-line |
| 3 | Inside delta |
Manual · PDF 93 · 20G – External Bypass
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Disable (default) |
| 2 | Enable |
Manual · PDF 94 · 40A – Ground Fault Level
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 0 A - 50 A | 0 A |
Manual · PDF 94 · 40B – Ground Fault Delay
Exact parameter range and default as printed; not commissioned values. Retain all source descriptions, units, exceptions and warnings.
| Source row | Range | Default |
|---|---|---|
| 1 | 00:00 – 01:30 mm:ss | 1 second |
Manual · PDF 94 · 20H – Shunt Trip Mode
Every row is one independent alternative. Physical side-by-side columns are not paired. Default markers kept exactly, including supplier contradictions.
| Source row | Alternative option |
|---|---|
| 1 | Disable (default) |
| 2 | Enable |
Manual · PDF 94 · 40C – Ground Fault Trip Active
Each option mapped to its own source meaning. Option defaults and restrictions retained verbatim. Continuation on adjacent source pages explicitly identified.
| Source row | Option | Meaning |
|---|---|---|
| 1 | Always Active | A trip can occur at any time when the soft starter is receiving power. |
| 2 | Operating Only (default) | A trip can occur while the soft starter is running, stopping or starting. |
| 3 | Run Only | A trip can only occur while the soft starter is running. |
Manual · PDF 95 · 40D – Ground Fault Action
Source-specific values and full associated procedure/conditions. Physical alternatives are separate options, not paired columns.
| Source row | Alternative |
|---|---|
| 1 | Soft Trip and Log (default) |
| 2 | Soft Trip and Reset |
| 3 | Trip Starter |
| 4 | Trip and Reset |
| 5 | Warn and Log |
| 6 | Log Only |
| 7 | Trip + Shunt Relay |
Manual · PDF 95 · 40E – Ground Fault CT Ratio
Source-specific values and full associated procedure/conditions. Physical alternatives are separate options, not paired columns.
| Source row | Alternative |
|---|---|
| 1 | 1000:1 |
| 2 | 2000:1 (default) |
Manual · PDF 95 · 41A – Analog calibration
Source-specific values and full associated procedure/conditions. Physical alternatives are separate options, not paired columns.
| Source row | Range | Default |
|---|---|---|
| 1 | 90% - 110% | 100% |
Manual · PDF 95 · 41B – Analog calibration
Source-specific values and full associated procedure/conditions. Physical alternatives are separate options, not paired columns.
| Source row | Range | Default |
|---|---|---|
| 1 | 90% - 110% | 100% |
Manual · PDF 96 · Trip messages
Source-specific values and full associated procedure/conditions. Physical alternatives are separate options, not paired columns.
| Source row | Display | Possible cause/Suggested solution |
|---|---|---|
| 1 | 2 Phase - Damaged SCR | This message is displayed if the soft starter tripped on “ Lx-Tx shorted” during the pre-start checks and PowerThrough is enabled. It indicates that the starter now operates in PowerThough mode (2-phase control only). Check for either a shorted SCR or a short within the bypass contactor. Related parameters: 6S |
| 2 | Battery/clock | A verification error has occurred on the real time clock, or the backup battery voltage is low. If the battery is low and the power is off, date/time settings will be lost. The soft starter will continue to soft start and soft stop correctly. Reprogram the date and time. The battery is not removable. In order to replace the battery, the main control PCB must be replaced. Related parameters: 6T |
| 3 | Bypass overload | This trip is not adjustable. Bypass overload protection protects the soft starter from severe operating overloads while running. The soft starter will trip if it detects overcurrent at 600% of the contactor rating. Related parameters: None |
| 4 | Current at Stop | The soft starter has detected current at a time when no current is expected (Ready, Not Ready or Tripped states). If the motor is connected inside delta (six-wire connection) and no main contactor is installed, a shorted SCR may be passing current to the motor. Related parameters: None |
Manual · PDF 97 · Trip messages
Source-specific values and full associated procedure/conditions. Physical alternatives are separate options, not paired columns.
| Source row | Display | Possible cause/Suggested solution |
|---|---|---|
| 1 | Current imbalance | Current imbalance can be caused by problems with the motor, the environment or the installation, such as: An imbalance in the incoming mains voltage A problem with the motor windings A light load on the motor A phase loss on input terminals L1, L2 or L3 during Run mode An SCR that has failed open circuit. A failed SCR can only be definitely diagnosed by replacing the SCR and checking the starter's performance. Related parameters: 5A, 5B, 6C |
| 2 | Current Read Err Lx | Where 'X' is 1, 2 or 3. Internal fault (PCB fault). The output from the CT circuit is not close enough to zero when the SCRs are turned off. Contact your local supplier for advice. Related parameters: None |
| 3 | Depth Sensor | The smart card has detected a fault with the depth sensor. Related parameters: 30L, 36C |
| 4 | EEPROM fail | An error occurred loading data from the EEPROM to RAM when the keypad powered up. If the problem persists, contact your local distributor. Related parameters: None |
| 5 | Excess start time | Excess start time trip can occur in the following conditions: parameter 1B Motor Full Load Current is not appropriate for the motor parameter 2D Current Limit has been set too low parameter 2B Start Ramp Time has been set greater than the setting for 5O Excess Start Time parameter 2B Start Ramp Time is set too short for a high inertia load when using Adaptive Control Related parameters: 1B, 2B, 2D, 3D, 3F |
| 6 | Firing Fail Px | Where 'X' is phase 1, 2 or 3. The SCR did not fire as expected. The SCR may be faulty or there may be an internal wiring fault. Related parameters: None |
| 7 | FLC too high | The soft starter can be used on a motor with a higher full load current (FLC) if it is connected inside delta, or if a non-bypassed soft starter is installed with an external bypass contactor. If this trip occurs when the soft starter is installed inside delta, the soft starter may not be correctly detecting the connection. Set parameter 20F Motor Connection to ‘Inside Delta’. If the starter is a non-bypassed model and was previously used with an external bypass contactor, but parameter 20G External Bypass has now been set to ‘Disable’, the FLC may be above the maximum non-bypassed rating. Check that the non- bypassed rating of the soft starter is suitable for the motor, then set parameter 1B Motor Full Load Current to match the motor’s FLC. Related parameters: 1B, 20F, 20G |
Manual · PDF 98 · Trip messages
Source-specific values and full associated procedure/conditions. Physical alternatives are separate options, not paired columns.
| Source row | Display | Possible cause/Suggested solution |
|---|---|---|
| 1 | Flow Sensor | The smart card has detected a fault with the flow sensor. Related parameters: 30E, 36B |
| 2 | Flow Switch | The flow switch sensor (smart card terminals C23, C24) has closed. Related parameters: 30E, 36H |
| 3 | Frequency | This trip is not adjustable. The mains frequency has gone beyond the specified range. Check for other equipment in the area that could be affecting the mains supply, particularly variable speed drives and switch mode power supplies (SMPS). If the soft starter is connected to a generator set supply, the generator may be too small or could have a speed regulation problem. Related parameters: 6O |
| 4 | Ground Fault | Test the insulation of the output cables and the motor. Identify and resolve the cause of any ground fault. Related parameters: 40A, 40B, 40C, 40D, 40E |
| 5 | Heatsink overtemperature | Check that bypass contactors are operating. Check that cooling fans are operating (if fitted). If mounted in an enclosure, check if ventilation is adequate. The soft starter must be mounted vertically. Related parameters: None |
| 6 | High Flow | The flow sensor connected to the smart card has activated high flow protection. Related parameters: 30E, 30G, 30H, 31A, 31C, 31D, 36F |
| 7 | High Pressure | The pressure sensor connected to the smart card has activated high pressure protection. Related parameters: 30A, 30C, 30D, 32A, 32B, 32C, 36D |
| 8 | Input A trip Input B trip | The soft starter's programmable input is set to a trip function and has activated. Resolve the trigger condition. Related parameters: 7A, 7B, 7C, 7D, 7E, 7F, 7G, 7H |
| 9 | Instantaneous overcurrent | This trip is not adjustable. The current on all three phases has exceeded 7.2 times the value of parameter 1B Motor Full Load Current. Causes can include a locked rotor condition or an electrical fault in the motor or cabling. Related parameters: None |
| 10 | Internal fault x | Where 'X' is a number. This trip is not adjustable. The soft starter has tripped on an internal fault. Contact your local supplier with the fault code (X). |
| 11 | Internal fault 88 | The soft starter firmware does not match the hardware. |
Manual · PDF 99 · Trip messages
Source-specific values and full associated procedure/conditions. Physical alternatives are separate options, not paired columns.
| Source row | Display | Possible cause/Suggested solution |
|---|---|---|
| 1 | Keypad disconnected | Parameter 1A Command Source is set to Remote Keypad but the soft starter cannot detect a remote keypad. If a remote keypad is installed, check the cable is firmly connected to the soft starter. If no remote keypad is installed, change the setting of parameter 1A. Related parameters: 1A |
| 2 | L1 phase loss L2 phase loss L3 phase loss | This trip is not adjustable. During pre-start checks the starter has detected a phase loss as indicated. In run state, the starter has detected that the current on the affected phase has dropped below 10% of the programmed motor FLC for more than 1 second, indicating that either the incoming phase or connection to the motor has been lost. Check the supply and the input and output connections at the starter and at the motor end. Related parameters: None |
| 3 | L1-T1 shorted L2-T2 shorted L3-T3 shorted | During pre-start checks the starter has detected a shorted SCR or a short within the bypass contactor as indicated. Consider using PowerThrough to allow operation until the starter can be repaired. Related parameters: 6S |
| 4 | Low Control Volts | The soft starter has detected a drop in the internal control voltage. Check the external control supply (A1, A2, A3) and reset the starter. If the external control supply is stable: the 24 V supply on the main control PCB may be faulty; or the bypass driver PCB may be faulty. Contact your local supplier for advice. This protection is not active in Ready state. Related parameters: None |
| 5 | Low Flow | The flow sensor connected to the smart card has activated low flow protection. Related parameters: 30E, 30G, 30H, 31B, 31C, 31D, 36G |
| 6 | Low Pressure | The pressure sensor connected to the smart card has activated low pressure protection. Related parameters: 30A, 30C, 30D, 32D, 32E, 32F, 36E |
| 7 | Low Water | The depth sensor connected to the smart card has activated depth protection. Related parameters: 30L, 30N, 30O, 34A, 34B, 34C, 36I |
| 8 | Motor connection Motor Connection T1 Motor Connection T2 Motor Connection T3 | This trip is not adjustable. The motor is not connected correctly to the soft starter. Check individual motor connections to the soft starter for power circuit continuity. Check connections at the motor terminal box. If the soft starter is connected to a grounded delta mains supply, adjust parameter 20F Motor Connection to match the motor connection configuration. Related parameters: 20F |
Manual · PDF 100 · Trip messages
Source-specific values and full associated procedure/conditions. Physical alternatives are separate options, not paired columns.
| Source row | Display | Possible cause/Suggested solution |
|---|---|---|
| 1 | Motor overload | The motor has reached its maximum thermal capacity. Overload can be caused by: The soft starter protection settings not matching the motor thermal capacity Excessive starts per hour or start duration Excessive current Damage to the motor windings Resolve the cause of the overload and allow the motor to cool. Related parameters: 1B, 1D, 1E, 1F, 5O, 6J NOTE Parameters 1D, 1E and 1F determine the trip current for motor overload protection. The default settings of parameters 1D, 1E and 1F provide Motor Overload Protection: Class 10, Trip Current 105% of FLA (full load amperage) or equivalent. |
| 2 | Motor thermistor | The motor thermistor input has been enabled and: The resistance at the thermistor input has exceeded 3.6 kΩ for more than one second. The motor winding has overheated. Identify the cause of the overheating and allow the motor to cool before restarting. The motor thermistor input has been opened. If thermistors have previously been connected to the soft starter but are no longer required, use the Thermistor Reset function to disable the thermistor. Related parameters: 6Q |
| 3 | Network communication | There is a network communication problem, or the network master may have sent a trip command to the starter. Check the network for causes of communication inactivity. Related parameters: 6M |
| 4 | Not ready | The reset input may be active. If the reset input is active, the starter will not operate. The soft starter may be waiting for the restart delay to elapse. The length of the restart delay is controlled by parameter 5P Restart Delay. Related parameters: 5P |
| 5 | Overcurrent | The current has exceeded the level set in parameter 5E Overcurrent for longer than the time set in parameter 5F Overcurrent Delay. Causes can include a momentary overload condition. Related parameters: 5E, 5F, 6E |
| 6 | Overpower | The motor has experienced a sharp rise in power. Causes can include a momentary overload condition which has exceeded the adjustable delay time. Related parameters: 5M, 5N, 6I |
| 7 | Overvoltage | There has been a voltage surge on the mains. Causes can include problems with a transformer tap regulator or off-loading of a large transformer load. Related parameters: 5I, 5J, 6G |
Manual · PDF 101 · Trip messages
Source-specific values and full associated procedure/conditions. Physical alternatives are separate options, not paired columns.
| Source row | Display | Possible cause/Suggested solution |
|---|---|---|
| 1 | Parameter out of range | This trip is not adjustable. A parameter value is outside the valid range. The keypad will indicate the first invalid parameter. An error occurred loading data from the EEPROM to RAM when the keypad powered up. The parameter set or values in the keypad do not match the parameters in the starter. "Load User Set" has been selected but no saved file is available. Reset the fault. The starter will load the default settings. If the problem persists, contact your local distributor. Related parameters: None |
| 2 | Phase sequence | The phase sequence on the soft starter's input terminals (L1, L2, L3) is not valid. Check the phase sequence on L1, L2, L3 and ensure the setting in parameter 5R is suitable for the installation. Related parameters: 5R, 6P |
| 3 | Power loss | This trip is not adjustable. The starter is not receiving mains supply on one or more phases. Check that the main contactor closes when a start command is given, and remains closed until the end of a soft stop. Check the fuses. If testing the soft starter with a small motor, it must draw at least 10% of the starter's programmed FLC setting on each phase. If shunt relay mode is enabled (parameter 20H Shunt Trip Mode), certain trips may cause the shunt relay to open the circuit breaker. Related parameters: None |
| 4 | Pressure Sensor | The smart card has detected a fault with the pressure sensor. Related parameters: 30A, 36A |
| 5 | Rating Capacity | The soft starter is operating beyond its safe capacity. Allow the starter to cool. Related parameters: None |
| 6 | RTD Circuit | The smart card has detected a fault with the RTD sensor, or the RTD has activated temperature protection. Related parameters: 35B, 36J |
| 7 | SCR Itsm | The SCR current surge rating has been exceeded. Related parameters: None |
| 8 | SCR overtemperature | The temperature of the SCRs, calculated by the thermal model, is too high to allow further operation. Wait for the starter to cool. Related parameters: None |
| 9 | Starter communication | There is a problem with the connection between the soft starter and the optional expansion card. Remove and reinstall the card. If the problem persists, contact your local distributor. Related parameters: None |
| 10 | Starts per hour | The soft starter has already attempted the maximum number of starts in the last 60 minutes. Wait before attempting another start. To determine when the waiting period will end, review the log. Related parameters: 5Q |
Manual · PDF 102 · Trip messages
Source-specific values and full associated procedure/conditions. Physical alternatives are separate options, not paired columns.
| Source row | Display | Possible cause/Suggested solution |
|---|---|---|
| 1 | Thermistor circuit | The thermistor input has been enabled and: The resistance at the input has fallen below 20 Ω (the cold resistance of most thermistors will be over this value) or A short circuit has occurred. Check and resolve this condition. Related parameters: None |
| 2 | Time-overcurrent | The soft starter is internally bypassed and has drawn high current during running. (The 10A protection curve trip has been reached or the motor current has risen to 600% of the motor FLC setting.) Related parameters: None |
| 3 | Undercurrent | The motor has experienced a sharp drop in current, caused by loss of load. Causes can include broken components (shafts, belts or couplings), or a pump running dry. Related parameters: 5C, 5D, 6D |
| 4 | Underpower | The motor has experienced a sharp drop in power, caused by loss of load. Causes can include broken components (shafts, belts or couplings), or a pump running dry. Related parameters: 5K, 5L, 6H |
| 5 | Undervoltage | Mains voltage has fallen below the level selected. Causes can include an undersized supply or adding a large load to the system. Related parameters: 5G, 5H, 6F |
| 6 | Unsupported option | The selected function is not available (eg jog is not supported in inside delta configuration). Related parameters: None |
| 7 | VZC Fail Px | Where 'X' is 1, 2 or 3. Internal fault (PCB fault). Contact your local supplier for advice. Related parameters: None |
| 8 | Zero Speed Detect | The zero speed input has not closed within the expected duration of a soft stop. Check the zero speed sensor is operating correctly. Check that parameters 2Q Brake Current Limit and 5O Excess Start Time are appropriate for the application. Related parameters: 2Q, 3S, 5O |
Manual · PDF 102 · General faults
Source-specific values and full associated procedure/conditions. Physical alternatives are separate options, not paired columns.
| Source row | Symptom | Probable Cause |
|---|---|---|
| 1 | Starter "Not Ready" | The reset input may be active. If the reset input is active, the starter will not operate. |
| 2 | "Simul" on display | The starter is running simulation software. This software is intended for demonstration purposes only and is not suitable for controlling a motor. Contact your local supplier for advice. |
| 3 | The soft starter does not respond to the START or RESET button on the remote keypad. | The soft starter will only accept commands from the keypad if parameter 1A Command Source is set to Remote Keypad. Check that the Local LED on the starter is on. |
Manual · PDF 103 · General faults
Source-specific values and full associated procedure/conditions. Physical alternatives are separate options, not paired columns.
| Source row | Symptom | Probable Cause |
|---|---|---|
| 1 | The soft starter does not respond to commands from the control inputs. | The soft starter will only accept commands from the inputs if parameter 1A Command Source is set to Digital Input. Check the setting of 1A. The control wiring may be incorrect. Check that the remote start, stop and reset inputs are configured correctly (see on Start/Stop page 27 for details). The signals to the remote inputs may be incorrect. Test the signalling by activating each input signal in turn. |
| 2 | The soft starter does not respond to a start command from either the keypad or the digital inputs. | The soft starter may be waiting for the restart delay to elapse. The length of the restart delay is controlled by parameter 5P Restart Delay. The motor may be too hot to permit a start. The soft starter will only permit a start when it calculates that the motor has sufficient thermal capacity to complete the start successfully. Wait for the motor to cool before attempting another start. The reset input may be active. If the reset input is active, the starter will not operate. The soft starter may be waiting for control signals via the communications network (parameter 1A Command Source = Network). The soft starter may be waiting for a scheduled auto-start (parameter 1A Command Source = Clock). |
| 3 | Erratic and noisy motor operation. | If the soft starter is connected to the motor using inside delta configuration, the soft starter may not be correctly detecting the connection. Contact your local supplier for advice. |
| 4 | Remote keypad shows message "awaiting data" | The keypad is not receiving data from the control PCB. Check the cable connection. |
| 5 | The soft starter does not control the motor correctly during starting. | Start performance may be unstable when using a low Motor Full Load Current setting (parameter 1B). Power factor correction (PFC) capacitors must be installed on the supply side of the soft starter and must be disconnected during starting and stopping. To use the soft starter to control power factor correction, connect the PFC contactor to a programmable relay set to Run. High levels of harmonics on the mains supply can affect soft starter performance. If variable speed drives are installed nearby, check they are properly grounded and filtered. |
Manual · PDF 104 · General faults
Source-specific values and full associated procedure/conditions. Physical alternatives are separate options, not paired columns.
| Source row | Symptom | Probable Cause |
|---|---|---|
| 1 | Motor does not reach full speed. | If the start current is too low, the motor will not produce enough torque to accelerate to full speed. The soft starter may trip on excess start time. NOTE Make sure the motor starting parameters are appropriate for the application and that you are using the intended motor starting profile. If a programmable input is set to Motor Set Select, check that the corresponding input is in the expected state. The load may be jammed. Check the load for severe overloading or a locked rotor situation. |
| 2 | Soft stop ends too quickly. | The soft stop settings may not be appropriate for the motor and load. Review the soft stop settings. If the motor is very lightly loaded, soft stop will have limited effect. |
| 3 | After selecting Adaptive Control the motor used an ordinary start and/or the second start was different to the first. | The first Adaptive Control start is actually 'Constant Current' so that the starter can learn from the motor characteristics. Subsequent starts use Adaptive Control. |
| 4 | PowerThrough does not operate when selected. | The starter will trip on Lx-Tx Shorted on the first start attempt after control power is applied. PowerThrough will not operate if control power is cycled between starts. |
| 5 | Parameter settings cannot be stored. | Make sure you are saving the new value by pressing the button MENU/ENTER after adjusting a parameter setting. If you press RESET/EXIT, the change will not be saved. The soft starter does not display a confirmation. Check that the adjustment lock (parameter 10G) is set to Read & Write. If the adjustment lock is set to Read Only, settings can be viewed but not changed. |
| 6 | USB Full | The USB drive may not have enough free space available for the selected function. The file system on the USB drive may not be compatible with the soft starter. The soft starter supports FAT32 file systems. The soft starter's USB functions are not compatible with NTFS file systems. |
| 7 | USB Missing | A USB function has been selected in the menu, but the product cannot detect a USB drive. Check that the USB drive has been inserted in the port. |
| 8 | File Missing | A USB function has been selected in the menu, but the required file cannot be found. Save/Load Master Parameters uses a file called Master_Parameters.par, at the top level of the USB drive. For these functions to work correctly, do not move or rename this file. |
| 9 | File Not Valid | A USB function has been selected in the menu, but the file is not valid. |
Manual · PDF 105 · General faults
Source-specific values and full associated procedure/conditions. Physical alternatives are separate options, not paired columns.
| Source row | Symptom | Probable Cause |
|---|---|---|
| 1 | File Empty | A USB function has been selected in the menu and the file has been found, but does not contain the expected content. |
| 2 | Rating Not Valid | The value of parameter 20D Model Rating is incorrect. Parameter 20D is not user-adjustable. Contact your local supplier for advice. |
Manual · PDF 108 · Source contact blocks
Seven physical blocks. NZ location suffixes are editorial disambiguation. SA/NT has mobile/phone/email but no address. Omitted fields are not source blanks.
| Source row | Source location/context | Entity | Address | Phone | Mobile | Fax | Website | |
|---|---|---|---|---|---|---|---|---|
| 1 | HEAD OFFICE AUSTRALIA | TECO Australia Pty Limited | 335-337 Woodpark Road,Smithfield NSW2164 | +61 2 9765 8118 | [not printed] | +61 2 9765 8185 | sales.nsw@teco.com.au | www.teco.com.au |
| 2 | VIC/TAS | TECO Australia Pty Limited | 16 Longstaff Road,Bayswater VIC3153 | +61 3 9720 4411 | [not printed] | [not printed] | vicsales@teco.com.au | [not printed] |
| 3 | SA/NT | TECO Australia Pty Limited | [not printed] | +61 3 9720 4411 | +61 423 480 965 | [not printed] | vicsales@teco.com.au | [not printed] |
| 4 | NEW ZEALAND / Rolleston | TECO New Zealand Ltd | 11 Container Drive,Rolleston,Canterbury7614 | +64 3 271 8480 | [not printed] | [not printed] | sales@teco.co.nz | [not printed] |
| 5 | WA | TECO Australia Pty Limited | 18 Hazelhurst Street,Kewdale WA6105 | +61 8 9479 4879 | [not printed] | [not printed] | sales.wa@teco.com.au | [not printed] |
| 6 | QLD | TECO Australia Pty Limited | 50 Murdoch Circuit,Acacia Ridge QLD4110 | +61 7 3373 9600 | [not printed] | [not printed] | sales.qld@teco.com.au | [not printed] |
| 7 | NEW ZEALAND / Penrose | TECO New Zealand Ltd | 4 Autumn Place,Penrose,Auckland1061 | +64 9 526 8480 | [not printed] | [not printed] | sales@teco.co.nz | [not printed] |
Brochure · PDF 6 · Application guidance
Context: Recommendations are supplier application guidance and retain their conditional wording; they do not prove selection for an unspecified installation.
Table conditions: Textual sequence arrows are as printed; no wiring topology inferred.
| Application | Printed system sequence | Supplier application explanation | Recommended solution / exact scope |
|---|---|---|---|
| Pumping Systems | Power Supply → Soft Starter → Motor → Pump → Pipeline | Controlled motor acceleration helps reduce hydraulic shock and pressure transients in pumping systems, improving pipeline stability during startup and shutdown. | TECO RSXi or TECO TSXi depending on system complexity. |
| Conveyor Systems | Power Supply → Soft Starter → Motor → Conveyor → Material Load | Gradual motor acceleration reduces belt tension and mechanical stress in conveyor systems transporting heavy materials. This improves mechanical stability during startup and reduces drivetrain stress in heavily loaded systems. | TECO TSXi. |
| Crushers and Mills | Power Supply → Soft Starter → Motor → Crusher / Mill | High-inertia loads require controlled torque transfer during motor startup to improve drivetrain stability. | TECO TSXi. |
| Compressors and Fans | Power Supply → Soft Starter → Motor → Compressor / Fan | Compressors and ventilation fans often require smooth motor acceleration to reduce mechanical stress and maintain stable system operation during startup and stopping. | TECO RSXi or TECO TSXi depending on motor size and control requirements. |
| High-Power Industrial Systems | Power Supply → Soft Starter → Motor → Heavy Conveyor / Pump | Large industrial installations operating at high power levels require controlled motor starting and stopping to reduce electrical and mechanical stress. | TECO TSXi-1200V. |
Brochure · PDF 12 · TSXi electrical operating range
Context: Source page12 says Motor thermistat input; page14 uses Motor thermistor input. Literal wording preserved without deciding whether these describe a different device.
Context: V5 is named standard for New Zealand and V7 for Australia here; page16 labels380–690VAC Standard ANZ. Preserve source scopes separately.
Context: Page12 prints programmable inputB at13,14, whereas page14 prints13,15. Retain both page-specific statements; do not select a wiring interpretation.
Table conditions: Source family/configuration-specific values; no tolerance imported from RSXi.
| Item | Code / context | Value | Source applicability |
|---|---|---|---|
| Current range | [no code printed] | 24 A –1250 A | TSXi |
| Operating voltage | V5 | 3 ×200–525 VAC (+10% /−15%) | Standard configuration for New Zealand |
| Operating voltage | V7 | 3 ×380–690 VAC (+10% /−15%) | Standard configuration for Australia |
| Control voltage | C1 | 110–120 VAC or220–240 VAC | No tolerance printed here |
| Optional control voltage | C2 | 24 VAC /24 VDC | Optional; no tolerance printed here |
Brochure · PDF 12 · Printed IO reference
Context: Source page12 says Motor thermistat input; page14 uses Motor thermistor input. Literal wording preserved without deciding whether these describe a different device.
Context: V5 is named standard for New Zealand and V7 for Australia here; page16 labels380–690VAC Standard ANZ. Preserve source scopes separately.
Context: Page12 prints programmable inputB at13,14, whereas page14 prints13,15. Retain both page-specific statements; do not select a wiring interpretation.
Table conditions: Literal table, including duplicate13,14 labels; source photograph settings and wiring geometry remain original.
| Terminal label | Description |
|---|---|
| B4,B5 | Motor thermistat input |
| 10,11 | Reset input |
| 11,12 | Start/stop input |
| 13,14 | Programmable input A (default = Input Trip (N/O)) |
| 13,14 | Programmable input B (default = Input Trip (N/O)) |
| [USB symbol] | USB port |
| 21,22 | Analog output |
| 33,34 | Main contactor output |
| 41,42,44 | Relay output A (default = Run) |
| 53,54 | Relay output B (default = Run) |
| 03,04 | Bypass contactor output |
Brochure · PDF 13 · Starting methods
Context: Supplier feature statements are retained; no inside-delta current conversion or installation suitability is derived.
Table conditions: TSXi
| Listed item |
|---|
| Constant current start |
| Current ramp start |
| Adaptive control start |
Brochure · PDF 13 · Stopping methods
Context: Supplier feature statements are retained; no inside-delta current conversion or installation suitability is derived.
| Listed item |
|---|
| Adaptive stop |
| Soft brake |
| DC brake |
Brochure · PDF 13 · Integrated Motor Protection
Context: Supplier feature statements are retained; no inside-delta current conversion or installation suitability is derived.
Table conditions: TSXi; no unstated threshold values
| Listed item |
|---|
| Integrated thermal motor modelling |
| Programmable trip classes |
| Over- and under-voltage monitoring |
| Over- and under-power monitoring |
| Configurable protection responses (trip, warning or log) |
Brochure · PDF 13 · Monitoring and Diagnostics
Context: Supplier feature statements are retained; no inside-delta current conversion or installation suitability is derived.
| Listed item |
|---|
| Event logging (up to384 events) |
| Real-time clock with trip logging |
| Integrated metering and monitoring |
| USB parameter backup and firmware update |
Brochure · PDF 13 · Available interfaces
Context: Supplier feature statements are retained; no inside-delta current conversion or installation suitability is derived.
Table conditions: Optional modules, not built-in all-unit ports
| Listed item |
|---|
| Modbus RTU |
| Modbus TCP |
| Ethernet/IP |
| Profibus |
| Profinet |
| DeviceNet |
Brochure · PDF 13 · Optional accessories
Context: Supplier feature statements are retained; no inside-delta current conversion or installation suitability is derived.
Table conditions: Optional accessories
| Listed item |
|---|
| Remote keypad and operator interfaces |
| Communication interface cards |
| Smart Card modules for application-specific control, including pumping applications |
Brochure · PDF 13 · Typical applications
Context: Supplier feature statements are retained; no inside-delta current conversion or installation suitability is derived.
Table conditions: Supplier typical uses
| Listed item |
|---|
| Industrial conveyors |
| Crushers and mills |
| Pumping systems |
| Compressors |
Brochure · PDF 13 · Printed automation sequence
Context: Supplier feature statements are retained; no inside-delta current conversion or installation suitability is derived.
Table conditions: Illustrative labelled integration flow; no protocol compatibility beyond printed modules inferred.
| Context | Labels |
|---|---|
| Upper | PLC / Control System |
| Middle | Power Supply → TECO TSXi → Motor → Load |
| Lower | SCADA / Monitoring |
Brochure · PDF 14 · Numbered circuit legend
Context: Source drawing reference17674.C; original retains circuit connectivity.
Context: InputB13,15 here differs from page12 inputB13,14. No repair inferred.
Context: Source wiring drawing retained in original; text below only preserves numbered and terminal legends. Circuit connectivity is not reconstructed.
Table conditions: TSXi source drawing; not wiring instructions independent of image.
| Number | Description |
|---|---|
| 1 | Three-Phase Supply |
| 2 | Motor |
| 3 | Control voltage (soft starter) |
| 4 | Digital inputs |
| 5 | Motor thermistor input |
| 6 | Relay outputs |
| 7 | Analog output |
| 8 | Control voltage (external equipment) |
| 9 | Pilot lamps |
| 10 | Communications / Smart card expansion port |
Brochure · PDF 14 · Terminal and component legend
Context: Source drawing reference17674.C; original retains circuit connectivity.
Context: InputB13,15 here differs from page12 inputB13,14. No repair inferred.
Context: Source wiring drawing retained in original; text below only preserves numbered and terminal legends. Circuit connectivity is not reconstructed.
Table conditions: Source page14, separate from page12 contrary label.
| Label | Description |
|---|---|
| K1 | Main Contactor |
| F1 | Fuses or circuit breaker |
| 10,11 (S1) | Reset |
| 11,12 (S2) | Start/Stop |
| 13,14 | Programmable input A (default = Input Trip (N/O)) |
| 13,15 | Programmable input B (default = Input Trip (N/O)) |
| B4,B5 | Motor thermistor input |
| 33,34 | Main contactor output |
| 41,42,44 | Relay output A (default = Run) |
| 53,54 | Relay output B (default = Run) |
| 21,22 | Analog output |
Brochure · PDF 15 · TSXi model dimensions and weights
Context: A/B are width, C/D height, E depth inmm. Weight inkg. No current rating inferred from model number; dimensional drawings retained.
Context: Five dimension columns and weight column have independent merged-cell extents. Rows below explicitly repeat the printed shared cells per named model, preserving all B/C suffixes.
Table conditions: Source-merged values explicitly associated with each physical model row. No blank-source values inferred; values apply only to listed model.
| MODEL | Width A(mm) | Width B(mm) | Height C(mm) | Height D(mm) | Depth E(mm) | Weight(kg) |
|---|---|---|---|---|---|---|
| 0024B | 152 | 92 | 336 | 307 | 233 | 4.8 |
| 0042B | 152 | 92 | 336 | 307 | 233 | 4.8 |
| 0052B | 152 | 92 | 336 | 307 | 233 | 4.9 |
| 0064B | 152 | 92 | 336 | 307 | 233 | 4.9 |
| 0069B | 152 | 92 | 336 | 307 | 233 | 4.9 |
| 0105B | 152 | 92 | 336 | 307 | 233 | 5.5 |
| 0115B | 152 | 92 | 336 | 307 | 233 | 5.5 |
| 0135B | 152 | 92 | 336 | 307 | 233 | 5.5 |
| 0184B | 216 | 180 | 495 | 450 | 245 | 12.7 |
| 0200B | 216 | 180 | 495 | 450 | 245 | 12.7 |
| 0229B | 216 | 180 | 495 | 450 | 245 | 12.7 |
| 0250B | 216 | 180 | 495 | 450 | 245 | 12.7 |
| 0352B | 216 | 180 | 523 | 450 | 245 | 15.5 |
| 0397B | 216 | 180 | 523 | 450 | 245 | 15.5 |
| 0410B | 216 | 180 | 523 | 450 | 245 | 15.5 |
| 0550B | 216 | 180 | 523 | 450 | 245 | 19.0 |
| 0580B | 216 | 180 | 523 | 450 | 245 | 19.0 |
| 0835B | 447 | 287 | 618 | 525 | 310 | 51.0 |
| 0940B | 447 | 287 | 618 | 525 | 310 | 51.0 |
| 1070B | 447 | 287 | 618 | 525 | 310 | 62.0 |
| 1230B | 447 | 287 | 618 | 525 | 310 | 63.0 |
| 1250B | 447 | 287 | 618 | 525 | 310 | 65.0 |
| 0735C | 447 | 287 | 618 | 525 | 310 | 47.0 |
| 0830C | 447 | 287 | 618 | 525 | 310 | 47.0 |
| 1025C | 447 | 287 | 618 | 525 | 310 | 58.0 |
| 1170C | 447 | 287 | 618 | 525 | 310 | 59.0 |
| 1220C | 447 | 287 | 618 | 525 | 310 | 61.0 |
Brochure · PDF 16 · Accessories
Context: Standard ANZ Voltage380–690VAC summary differs in scope from page12 New Zealand V5 and Australia V7 statements. Retain both; no silent resolution.
Context: Accessory0654B retained literally although absent from page15 model table. No equivalent model or fit inferred.
Table conditions: Optional accessories. IP20 is accessory kit scope, not all-unit enclosure rating.
| Listed item |
|---|
| Devicenet |
| Modbus RTU c/w Ground Fault |
| Modbus TCP c/w Ground Fault P4K IoT |
| Profinet c/w Ground Fault P4K IoT |
| Ethernet/IP c/w Ground Fault P4K IoT |
| Modbus RTU |
| Profibus |
| Remote Keypad Card |
| Remote Keypad Card & Keypad |
| Remote Keypad |
| Smart Card - Pump application |
| Kit Enclosure Opening Tools |
| Fingerguard kit IP20,0184B -0580B |
| Fingerguard Kit IP20,0654B -1250B |
Brochure · PDF 16 · TSXi Technical Summary
Context: Standard ANZ Voltage380–690VAC summary differs in scope from page12 New Zealand V5 and Australia V7 statements. Retain both; no silent resolution.
Context: Accessory0654B retained literally although absent from page15 model table. No equivalent model or fit inferred.
Table conditions: TSXi summary, no RSXi or TSXi-1200V inheritance.
| FEATURE | SPECIFICATION |
|---|---|
| Product Type | Industrial Soft Starter Solution |
| Control Topology | Three-phase SCR control with internal bypass |
| Current Range | 24 A –1250 A |
| Operating Voltage | 200–690 VAC (depending on voltage configuration) |
| Standard ANZ Voltage | 380–690 VAC |
| Control Voltage | 110–120 VAC or220–240 VAC |
| Optional Control Voltage | 24 VAC /24 VDC |
| Start Methods | Constant Current • Current Ramp • Adaptive Control |
| Stop Methods | Adaptive Stop • Soft Brake • DC Brake |
| Protection Functions | Thermal Motor Model • Voltage Monitoring • Power Monitoring |
| Diagnostics | Event Logging • RTC Trip Log |
| Communications | Optional communication interface modules |
| Integration | PLC / SCADA compatible |
Brochure · PDF 23 · Start with the motor supply voltage
These app links are reproduced from our brochure. Confirm current app availability before use.
Context: Supplier selection guide; preserve lower/upper bounds exactly and do not fill uncovered voltage or current combinations. No installation approval implied.
Table conditions: Source limits, not a comprehensive numerical selection algorithm.
| SUPPLY VOLTAGE | RECOMMENDED SOLUTION |
|---|---|
| Up to575 VAC | Up to575 VAC → RSXi for compact applications → TSXi for industrial systems |
| 575–690 VAC | TECO TSXi |
| 960–1320VAC | TECO TSXi-1200V |
Brochure · PDF 23 · Consider motor current and application size
These app links are reproduced from our brochure. Confirm current app availability before use.
Context: Supplier selection guide; preserve lower/upper bounds exactly and do not fill uncovered voltage or current combinations. No installation approval implied.
Table conditions: Preserve explicit1000VAC qualifier and overlapping200A boundary.
| MOTOR CURRENTS | RECOMMENDED SOLUTION |
|---|---|
| Up to200 A | TECO RSXi |
| 200 A –1250 A | TECO TSXi |
| 202 A –1092 A at1000VAC | TECO TSXi-1200V |
Brochure · PDF 23 · Evaluate application behaviour
These app links are reproduced from our brochure. Confirm current app availability before use.
Context: Supplier selection guide; preserve lower/upper bounds exactly and do not fill uncovered voltage or current combinations. No installation approval implied.
Table conditions: Guidance in this source, not universal exclusions or approval.
| APPLICATION REQUIREMENT | RECOMMENDED SOLUTION |
|---|---|
| Simple controlled starting and stopping | TECO RSXi |
| Replacement of direct-on-line starters | TECO RSXi |
| High inertia loads | TECO TSXi |
| Controlled stopping required | TECO TSXi |
| Braking functionality required | TECO TSXi |
| Adaptive acceleration / deceleration | TECO TSXi |
Brochure · PDF 23 · System integration requirements
These app links are reproduced from our brochure. Confirm current app availability before use.
Context: Supplier selection guide; preserve lower/upper bounds exactly and do not fill uncovered voltage or current combinations. No installation approval implied.
Table conditions: Source qualitative guidance.
| INSTALLATION TYPE | RECOMMENDED SOLUTION |
|---|---|
| Standard MCC installation | TECO RSXi or TECO TSXi |
| Engineered high-power motor control system | TECO TSXi-1200V |
Brochure · PDF 23 · MI-START encoded app destinations
These app links are reproduced from our brochure. Confirm current app availability before use.
Context: Supplier selection guide; preserve lower/upper bounds exactly and do not fill uncovered voltage or current combinations. No installation approval implied.
These app links are reproduced from our brochure. Confirm current app availability before use.
| Printed QR label | Encoded URL |
|---|---|
| Apple iOS | https://apps.apple.com/nz/app/mi-start-soft-starters/id6759537733 |
| Android | https://play.google.com/store/apps/details?id=com.mistart.starthere&pcampaignid=web_share |
Source notes and selection checks
Shared specifications are presented once, with the individual model sheets linked for reference. Distinct ratings and conditions remain separate.
Blank application fields remain blank; C-suffix manual configurations remain separately labelled; chart geometry is not converted into exact values. Manufacturer-marked compliance statements are not fresh certification checks.
Additional specification notes from the model sheets
Identical printed sections are shown once. Options are not assumed fitted; family statements apply only within their stated model range. These source extracts retain conflicting wording where present; see the selection checks above.
Optional accessories
Remote HMI Finger Guards Fieldbus Smart Cards
includes models protocols options
§ Status Indication § 0184B-0580B § Profibus
Profibus § Pump Card
§ Start/Stop/Reset § 0835B-1250B ProfiNet
§§ ProfiNet
§ Programming ModbusTCP
§§ Modbus TCP
§ Graphical Display § Modbus RTU
§ Hot Keys § DeviceNet
§ Ethernet IP
* Ground fault option available
Selection limitation
If the expected operational duty exceeds stated
starter capability shown above contact your local
representative who will verify correct starter selection.
INTERFACE
Plain Language display 8 Languages LED Status Indication Graphing
START / STOP FUNCTION
Voltage Ramp Start Constant Current Start Adaptive Start/Stop D.C. Brake
Kick Start Current Ramp Start Voltage Ramp Stop Soft Braking
Scheduled Start / Stop Reverse Direction
MOTOR AND SYSTEM PROTECTIONS
Motor Overload Current imbalance Phase Loss Underpower
Motor Connection Fault Overcurrent Phase Sequence Overpower
Instant Over Current (Jam) Undercurrent Undervoltage SCR Overload (ITSM)
Excess Start Time (Stall) External Trip Inputs Overvoltage Internal Bypass Overload
Too many starts Motor Thermistor Line Frequency
MONITORING
Phase currents Current phase imbalance Motor Power With PUMP SMART CARD
Average current Thermal Capacity: starter Power Factor § Pump Pressure
Hours Run Thermal Capacity: motor High current flag § Pump Flow
Start Counter Analogue Output Value Low current flag § Well depth
Line frequency Line-to-line voltage Motor temperature flag § Pump Temperature
Last Start Details Average voltage Ground Fault (Option)
ANCILLARY FUNCTIONS
Jog Emergency Mode Dual Motor Sets Programable Protection Action:
Inside Delta Operation Power-Through Mode Pump Clean • Soft Stop Trip
• Soft Stop Trip + Auto Reset
Motor Reverse Control Second Motor Set Run Timers • Trip
Restart Delay: Antibackspin Auto Reset Weekly Scheduling • Trip + Auto Reset
• Warn and Log
Auto-Start/Stop Soft Brake Control Simulation Tools
• Log Only
• Trip + Shunt relay Trip
ACTIVITY LOGS – 384 EVENTS
Date and Time Average Current Motor Thermistor State Rating Capacity
Event type Phase 1 Current Ambient Temp Voltage
Event Source Phase 2 Current Start Heatsink Temp Power Factor
Event Action Detail 1 Phase 3 Current Motor Thermal Models MI-START Support App
Event Action Detail 2 Frequency SCR Temp
Started in (s) Starter State At Event Bypass Contactor Temp
SUPPLY
Main Voltage L1,L2,L3 TSXi-xxxxB-V5 200~525 VAC (+/- 10%)
TSXi-xxxxB-V7 380~690 VAC (+/- 10%)
Control Voltage A1,A2,A3 TSXi-xxxxB-xx-C1 (A1, A2) 110~120 VAC (+10%/-15%), 600mA
TSXi-xxxxB-xx-C1 (A2, A3) 220~240 VAC (+10%/-15%), 600mA
TSXi-xxxxB-xx-C2 (A1, A2) 24 VAC/VDC (+/- 20%), 2.8A
Mains Frequency 50 Hz~60 Hz (+/- 5%)
Rated insulation 600 VAC to earth
Rated impulse withstand 6 kV
Form designation Bypassed semiconductor motor starter form 1
SHORT CIRCUIT CAPABILITY
Coordination with semiconductor fuses Type 1
Coordination with HRC fuses Type 2
ELECTROMAGNETIC CAPABILITY (COMPLIANT WITH EU DIRECTIVE 2014/35/EU)
EMC Immunity IEC 60947-4-2
EMC Emissions IEC 60947-4-2 Class B
INPUTS
Input rating Active 24 VDC, 8mA approx..
Motor thermistor (B4, B5) Trip >3.6 kΩ, reset <1.6 kΩ
OUTPUTS
Relay Outputs 10 A @ 250 VAC resistive, 5A @ 250 VAC AC15 pf 0.3
Main Contactor (33,34) Normally open
Relay output A (41, 42, 44) Changeover
Relay output B (53, 54) Normally open
Analog Output (21, 22) Maximum load 600Ω (12VDC @ 20 mA)
Accuracy +/- 5%
ENVIRONMENT
Operating Temperature -10oC~60oC above 40oC with derating
Storage Temperature -25oC~+60oC
Operating Altitude 0-1000m, above 1000m with derating
Humidity 5%~95% Relative Humidity
Pollution Degree Pollution Degree 3
Vibration IEC 60068-2-6
Protection 0024B~0135B IP20
0184B~1250B IP00
HEAT DISSIPATION
During Start 4.5 watts per ampere
During Run 0024B~0052B ≤ 35 watts approx. 0352B~0580B ≤ 140 watts approx.
0064B~0135B ≤ 50 watts approx. 0835B~1250B ≤ 180 watts approx.
0184B~0250B ≤ 120 watts approx.
APPROVALS
CE EN 60947-4-2 RCM IEC 60947-4-2
Product documents
- Soft-Starters-Brochure-PDF.pdf — Product page
- TECO-TSXi-user-manual.pdf — Product page
- TAC-EMD-Standard-Conditions-of-Sale-Final-May-2022.pdf — Shared website
- ISO9001-Intertek-SAI-Global-Certificate-QEC3088-Expiry-25-May-2029.pdf — Shared website
- ISO45001-Intertek-SAI-Global-Certificate-0185118-Expiry-22-August-2027.pdf — Shared website
- TSXi-0024B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0042B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0052B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0064B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0069B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0105B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0115B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0135B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0184B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0200B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0229B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0250B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0352B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0397B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0410B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0550B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0580B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0835B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-0940B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-1070B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-1230B-V7-C1-Soft-Starter.pdf — Technical row
- TSXi-1250B-V7-C1-Soft-Starter.pdf — Technical row
Our shared company certificates and conditions of sale remain separate from product-specific ratings. They do not certify an individual motor configuration.
Contact our team through the product page with your application, supply, required rating and mounting details.